Plan Review Notes
Plan Review Notes For Permit 03041303
Permit Number 03041303
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-08 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 ON EXISTING SERVICE AND INCLUDE ALL NEW
 LOADS.HEAT PUMP ETC.
  
 2)NOTE: PLEASE SEE WIRING DIAGRAM, DOES
 NOT INCLUDE HEAT PUMP/WIRING ETC.
 PLEASE SHOW.
  
 PLEASE NOTE, ALL PLANS DONE BY AN
 ENGINEER MUST CONTAIN ORIGINAL SIGNATURE
 (NOT COPIES) . FS/FAC 417.025/ 61G15-23
 -.002. SUBMITTALS ARE COPIES WITH A
 RAISED SEAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]