Plan Review Notes For Permit 03041296 |
Permit Number |
03041296 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-07 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-34SG WINDOW DOESN'T PROVIDE THE 24" | | CLEAR HEIGHT AS REQUIRED BY SECTION | | 1005.4 FBC 2001. REVISE AS REQUIRED. | | 2-REVISE/CLARIFY DETAIL S21 FOR COLUMN | | AT GARAGE AND STAIR WAY TO MATCH FLOOR | | PLAN CONDITIONS. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 3-REVISE CONNECTOR TC1 SPECIFIED FOR 2ND | | FLOOR WALL FRAMED WALL. NEED WOOD TO | | CONNECTOR. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC. |
|