Plan Review Notes For Permit 03041288 |
Permit Number |
03041288 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-REVISE/CLARIFY DETAIL S21 FOR COLUMN | | LOCATED BETWEEN GARAGE AND STAIRWAY TO | | MATCH CONDITIONS SHOWN ON 2ND FLOOR | | FRAMING PLAN. SECTION 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 2-ROOF FRAMING PLAN: REVISE CONNECTOR | | TC-1 SPECIFIED FOR FRAMED WALL. NEED | | WOOD TO WOOD CONNECTOR. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 3-34SH WINDOW DOESN'T PROVIDE THE 24" | | CLEAR OPENING REQUIRED BY SECTION | | 1005.4 FBC 2001. REVISE AS REQUIRED. |
|