Date |
Text |
2003-05-21 00:00:00 | 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) REVISE NOTE 11 UNDER PLAN NOTES ON |
| C1. HURRICANE PANELS ARE REQUIRED IN THE |
| CITY OF WPB WHICH IS NOT IN THE HVHZ, |
| BUT IS IN THE WIND BOURNE DEBRIS REGION. |
| SEE FBC 1606.1.4. |
| |
| 3) REVISE NOTE 15 UNDER FRAMING NOTES ON |
| C1. 3/8" HIGH RIB METAL LATH IS REQUIRED |
| TO BE FASTENED AT EACH RIB (4"O.C.) PER |
| ASTM C 1063. |
| |
| 4) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| 1/2" A.B. USED TO FASTEN THE 2X6 GARAGE |
| DOOR JAMB ON THE BUCK DETAIL ON A4. |
| |
| 5) CLARIFY ON THE BUCK DETAIL ON A4 THAT |
| THE SLIDING GLASS DOOR FRAME IS REQUIRED |
| TO BE FASTENED THROUGH THE 1X BUCK INTO |
| THE CONCRETE SUBSTRATE. FBC 1707.4.4.2 |
| |
| 6) REVISE THE TRUSS CONNECTOR SCHEDULE |
| ON A6. THE FBC DOES NOT ALLOW THE ONE- |
| THIRD INCREASE ON THE STEEL CALCULATIONS |
| SEE FBC 1609.4.3 AND THE 2003 USP |
| CATALOG. SOME OF THE CONNECTORS ARE |
| SPECIFIED WITH MORE FASTENERS THAN THE |
| AMOUNT LISTED IN THE CATALOG. INCREASING |
| THE NUMBER OF FASTENERS TO MORE THAN |
| SPECIFIED IN THE CATALOG WILL NOT |
| INCREASE THE UPLIFT VALUES BECAUSE THE |
| STEEL OF THE CONNECTOR WILL FAIL. |
| |
| 7) REVISE DETAIL 15 ON A5. THE MSH |
| CONNECTOR SPECIFIED IS A STRAP HANGER |
| AND IS NOT DESIGNED OR TESTED TO BE USED |
| OVER THE TRUSS AS A HOLD DOWN. THE |
| MAXIMUM NUMBER OF FASTENERS FOR A "USP" |
| TA14R IS (7). THE UPLIFT FOR DOUBLE |
| STRAPS IS 1720#. SEE 2003 USP CATALOG. |
| |
| 8) REVISE DETAIL 14 ON A5. THE MAXIMUM |
| NUMBER OF FASTENERS IS (7). REVIEW THE |
| UPLIFT VALUE SPECIFIED. |
| |
| 9) REVISE DETAIL 8 ON A5. THE MSTA18 |
| STRAP HAS A MAXIMUM UPLIFT VALUE OF |
| 1065# WITH (7) 10D NAILS EACH MEMBER PER |
| 2003 USP CATALOG. LARGER NAILS OR MORE |
| NAILS THAN SPECIFIED IN THE CATALOG WILL |
| NOT INCREASE THE UPLIFT VALUE. NOTE: THE |
| TOTAL NUMBER OF HOLES IN THE STRAP IS 14 |
| |
| 10) DETAIL 6 ON A5 SPECIFIES A HANGER |
| THAT IS FASTENED TO A MASONRY WALL WITH |
| (2) 5/8" THROUGH BOLTS ON EACH SIDE. |
| PLEASE CLARIFY. |
| |
| 11) DETAIL 3 ON A5 SHOWS A TRUSS TO CONC |
| TIE BEAM CONNECTION. HOWEVER,THERE IS NO |
| BEAM AT THE LOCATION INDICATED ON THE |
| FRAMING PLAN. |
| |
| 12) THE ENERGY CALCULATIONS DO NOT |
| INCLUDE THE AREA OF CEILINGS THAT ARE |
| COFFERED OR THE KNEE WALLS WHERE THE |
| CEILING CHANGES ELEVATIONS. SEE FBC |
| CHAPTER 13 SECTION 604.1.A.1. |
| |
| 13) SUBMIT INSTALLATION SCHEDULE AND |
| KEY PLAN FOR STORM PANELS. |
| |
| 14) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR 30" DIAMETER FIXED GLASS |
| WINDOW. |
| |
| 15) THE SITE SPECIFIC PRODUCT APPROVAL |
| FORMS ARE REQUIRED TO BE SIGNED, SEALED |
| AND DATED BY THE DESIGNER OF RECORD AS |
| WELL AS THE ENGINEER CERTIFYING THE |
| PRODUCT. A SEALED LETTER FROM THE |
| DESIGNER OF RECORD REFERENCING THE |
| SPECIFIC PRODUCT AND SITE IS ACCEPTABLE. |
| SITE SPECIFIC PRODUCT APPROVALS (WHICH |
| ARE SEALED DOCUMENTS) WITH WHITEOUT |
| AND CHANGES WILL NOT BE ACCEPTED. |
| |
| 16) SUBMIT SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |