2003-08-13 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) 61G1-16.004 TITLE BLOCK REQUIRED ON
 ALL ARCHITECTURAL DRAWS ECT. SEE ATTACH-
 ED SHEET FOR REQUIREMENTS.
 2) WASH MACHINE SHALL NOT DRAIN INTO THE
 WET VENT OF THE BATHROOM GROUP. SECTION
 909.1. WASH MACHINE SHALL CONNECT DOWN-
 STREAM OF THE BATHROOM GROUP. SEE RED
 LINE CORRECTIONS.
  