2003-06-30 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| |
| 1) CALCULATIONS FOR PRIMARY AND SECOND- |
| ARY ROOF DRAINS INSUFFICIENT. SUBMIT |
| CALCULATIONS SHOWING SQUARE FOOTAGE FOR |
| THE FLAT ROOF. SHOW 1/2 AREA OF ALL |
| VERTICAL WALLS INCLUDING PARAPTES. SHOW |
| SQUARE FOOTAGE FOR ALL ROOF AREA THAT |
| DRAINS TO FLAT ROOF FROM ABOVE. 1106.2 |
| 1106.4 - SECTION 1106.6 |
| 2) SECONDARY DRAIN SHALL BE SIZED PER |
| SEC 1107.3. THE MINIMUM CROSS-SECTIONAL |
| AREA OF AN OVERFLOW SCUPPER SHALL BE 3 |
| TIMES THE CROSS-SECTIONAL AREA OF THE |
| PRIMARY ROOF DRAIN AND THE SCUPPER SHALL |
| HAVE A MINIMUM OPENING DIMENSION OF 4" |
| 3) SCUPPER OPENINGS SHALL BE LARGE |
| ENOUGH FOR COMBINED AREA OF PRIMARY AND |
| SECONDARY DRAINS, (SCUPPERS). SUBMIT A |
| DETAIL FOR SCUPPER OPENING SHOWING WIDTH |
| AND HEIGHT OF OPENING. SECION 104.2.1 |
| 4) THIS IS THE THIRD REJECTION OF THIS |
| PLAN FOR THE SAME REASON - PLEASE SEE |
| ATTACHED SHEET CONCERNING FLORIDA STATU- |
| TE 553.80(2)(B) |
| 5) THE INFORMATION SUBMITTED IS THE RE- |
| SULT OF THE CALCULATIONS, BUT NOT THE |
| ACTUAL CALCULATIONS. |
| ********WHEN RESUBMITTING PLANS********* |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |