Plan Review Notes
Plan Review Notes For Permit 03041216
Permit Number 03041216
Review Stop P
Sequence Number 3
Notes
Date Text
2003-06-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) CALCULATIONS FOR PRIMARY AND SECOND-
 ARY ROOF DRAINS INSUFFICIENT. SUBMIT
 CALCULATIONS SHOWING SQUARE FOOTAGE FOR
 THE FLAT ROOF. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPTES. SHOW
 SQUARE FOOTAGE FOR ALL ROOF AREA THAT
 DRAINS TO FLAT ROOF FROM ABOVE. 1106.2
 1106.4 - SECTION 1106.6
 2) SECONDARY DRAIN SHALL BE SIZED PER
 SEC 1107.3. THE MINIMUM CROSS-SECTIONAL
 AREA OF AN OVERFLOW SCUPPER SHALL BE 3
 TIMES THE CROSS-SECTIONAL AREA OF THE
 PRIMARY ROOF DRAIN AND THE SCUPPER SHALL
 HAVE A MINIMUM OPENING DIMENSION OF 4"
 3) SCUPPER OPENINGS SHALL BE LARGE
 ENOUGH FOR COMBINED AREA OF PRIMARY AND
 SECONDARY DRAINS, (SCUPPERS). SUBMIT A
 DETAIL FOR SCUPPER OPENING SHOWING WIDTH
 AND HEIGHT OF OPENING. SECION 104.2.1
 4) THIS IS THE THIRD REJECTION OF THIS
 PLAN FOR THE SAME REASON - PLEASE SEE
 ATTACHED SHEET CONCERNING FLORIDA STATU-
 TE 553.80(2)(B)
 5) THE INFORMATION SUBMITTED IS THE RE-
 SULT OF THE CALCULATIONS, BUT NOT THE
 ACTUAL CALCULATIONS.
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.