Plan Review Notes
Plan Review Notes For Permit 03041216
Permit Number 03041216
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) CALCULATIONS FOR PRIMARY AND SECOND-
 ARY ROOF DRAINS SHALL SHOW TOTAL SQUARE
 FEET BEING DRAINED. CALCULATIONS SHALL
 SHOW 1/2 AREA OF ALL VERTICAL WALLS,
 (1106.4), ALL AREA OF ALL ROOFS THAT
 DRAIN TO ROOF FROM ABOVE, (1106.2).
 SECTION 104.2.1. GUTTERS SHALL BE SIZED
 PER TABLE 1106.6 FOR PRIMARY DRAIN ONLY.
 2) SECONDARY DRAIN SHALL BE SIZED PER
 SECTION 1107.3. THE MINIMUM CROSS-SECT-
 IONAL AREA OF AN OVERFLOW SCUPPER SHALL
 BE THREE TIMES THE CROSS-SECTIONAL AREA
 OF THE PRIMARY ROOF DRAIN AND THE SCUPP-
 ER SHALL HAVE A MINIMUM OPENING DIMEN-
 SION OF 4 INCHES.
 3) SCUPPER OPENINGS SHALL BE LARGE
 ENOUGH FOR COMBINED AREA OF PRIMARY AND
 SECONDARY DRAINS, (SCUPPERS). PLEASE
 SUBMIT A DETAIL FOR SCUPPER OPENING,
 SHOWING WIDTH AND HEIGHT OF OPENING.
 SECTION 104.2.1
 4) THE PERSONAL SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS TO BE FILED FOR
 PUBLIC RECORD. 61G1-16.003
  