Plan Review Notes For Permit 03041216 |
Permit Number |
03041216 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-03 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE PANEL SCHEDULES AND LOAD | | CALCULATIONS FOR ALL EXISTING AND NEW | | LOADS BEING ADDED.THE PLAN SHOWS A NEW | | LAUNDRY BUT ONLY LISTS ONE WASHER AND | | DRYER IN THE CALCULATIONS.ALSO THERE IS | | A NEW AHU AND ONLY ONE IN THE CALCS. | | | | INDICATE THE SERVICE SIZE,FEEDER AND CO | | NDUIT SIZES ON THE RISER DIAGRAM PER | | 215-5. | | | | NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2',6',12' RULE PER 210-52. | | | | NOTE: PLEASE NOTE THAT ALL PLANS | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | ING A TITLE BLOCK, MUST BE SIGNED, | | DATEDAND SEALED BY THE ARCH/ENGINEER OF | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | PLEASE REMOVE THE SHEETS FROM THE PLANS | | THAT ARE BEING REVISED,AND INSERT | | REVISED SHEETS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|