Plan Review Notes
Plan Review Notes For Permit 03041216
Permit Number 03041216
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-3 PLEASE SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 FOR FLAT ROOFS. OPENINGS FOR DOWNSPOUTS
 SHALL BE SIZED FOR BOTH PRIMARY AND
 SECONDARY DRAINS.
 SHOW 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS. SHOW AREA OF ROOFS
 THAT DRAIN ONTO FLAT ROOF FROM ABOVE.
 SEE SECTIONS 1106 AND 1107 AND ALL SUB-
 SECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692