2004-08-26 00:00:00 | **** NOTE ****** | | FIRE PUMP DECREASED FROM 150HP TO 100HP | | THIS IS FOR ELECTRICAL REVISION OF RISER | | ONLY. FIRE PLANS WILL ALSO NEED TO BE | | REVISED, REVIEWED BY FIRE PLAN REVIEW | | FOR CODE COMPLIANCE. | | | | ***PLANS NOW MISSING NOTE FOR SIGNAGE | | AS ON PREVIOUS PLANS. | | 230.2E | | | | *** PLANS ALSO NOTED FOR FIRE PUMP CONT. | | TO MEET 230.76,230.79 AND 110.27 | | MUST HAVE MANUAL MEANS OF DISCONNECT. | | 230.76 | | THIS MANUAL MEANS OF DISCONNECT MUST BE | | RATED FOR THE LOAD SERVED. 230.79 | | THIS MEANS OF DISCONNECT MAY NOT EXPOSE | | LIVE PARTS. 110.27 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|