Plan Review Notes
Plan Review Notes For Permit 03041167
Permit Number 03041167
Review Stop E
Sequence Number 7
Notes
Date Text
2004-08-26 00:00:00**** NOTE ******
 FIRE PUMP DECREASED FROM 150HP TO 100HP
 THIS IS FOR ELECTRICAL REVISION OF RISER
 ONLY. FIRE PLANS WILL ALSO NEED TO BE
 REVISED, REVIEWED BY FIRE PLAN REVIEW
 FOR CODE COMPLIANCE.
  
 ***PLANS NOW MISSING NOTE FOR SIGNAGE
 AS ON PREVIOUS PLANS.
 230.2E
  
 *** PLANS ALSO NOTED FOR FIRE PUMP CONT.
 TO MEET 230.76,230.79 AND 110.27
 MUST HAVE MANUAL MEANS OF DISCONNECT.
 230.76
 THIS MANUAL MEANS OF DISCONNECT MUST BE
 RATED FOR THE LOAD SERVED. 230.79
 THIS MEANS OF DISCONNECT MAY NOT EXPOSE
 LIVE PARTS. 110.27
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  