Plan Review Notes For Permit 03041167 |
Permit Number |
03041167 |
|
Review Stop |
P |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2003-08-09 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 BLDG. | | FBC-2001 AMENDMENTS, ADMIN. | | CODE, CHAPTER 1 | | | | 1) SHT A.1 PER TABLE 1003.1 (BLDG) AND | | TABLE 403.1 (PLMBG) PLUS SQUARE FOOTAGE | | SUPPLIED BY ARCHITECT, 110726 (WHSE) | | MINUS OFFICE AREA OF 7,081 SQUARE FEET, | | 6 WATER CLOSETS ARE REQUIRED. 8 WERE | | PROVIDED BUT 3 DELETED, (TWO URNALS AND | | 1 WATER CLOSET), SO ONLY 5 ARE PROVIDED. | | 2) SHTS A.7 & A.13 DETAILS AND NOTE ON | | SHT A.13 INDICATE 7 DOWNSPOUTS & SCUPPER | | AREAS, BUT SHT P6 WITH THE ROOF DRAIN | | CALCULATIONS SHOW 11 SCUPPERS AND DOWN | | SPOUTS. PLEASE CLAIRFY. | | 3) SHT A.13 SHOWS 12" X 6" GUTTER, BUT | | SHT P6 SHOWS THE GUTTER TO BE 16"WX6"D | | PLEASE CLAIRFY. | | 4) PROVIDE ELEVATION FOR GUTTER SHOWING | | PITCH TO DOWNSPOUTS, (SLOPE), ON SOUTH | | SIDE OF BLDG. | | 5) SHTS A.13 & P6. A.13 SHOWS 9 DOWN- | | SPOUTS ON SOUTH SIDE AND SHT P6 SHOWS | | 11 DOWNSPOUTS. PLEASE CLAIRFY | | 6) SHT P6 STILL SHOWS URNALS IN MEN'S | | TOILET ROOMS. | | 7) SHT P4 REVISION DELETED GASOLINE, OIL | | SANT INTECEPTOR WITH CALCULATIONS AND | | THE SUMP PUMP DETAIL. PLEASE CLAIRFY. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|