Plan Review Notes For Permit 03041167
Permit Number 03041167
Review Stop P
Sequence Number 5
Notes
Date Text
2003-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BLDG.
 FBC-2001 AMENDMENTS, ADMIN.
 CODE, CHAPTER 1
  
 1) SHT A.1 PER TABLE 1003.1 (BLDG) AND
 TABLE 403.1 (PLMBG) PLUS SQUARE FOOTAGE
 SUPPLIED BY ARCHITECT, 110726 (WHSE)
 MINUS OFFICE AREA OF 7,081 SQUARE FEET,
 6 WATER CLOSETS ARE REQUIRED. 8 WERE
 PROVIDED BUT 3 DELETED, (TWO URNALS AND
 1 WATER CLOSET), SO ONLY 5 ARE PROVIDED.
 2) SHTS A.7 & A.13 DETAILS AND NOTE ON
 SHT A.13 INDICATE 7 DOWNSPOUTS & SCUPPER
 AREAS, BUT SHT P6 WITH THE ROOF DRAIN
 CALCULATIONS SHOW 11 SCUPPERS AND DOWN
 SPOUTS. PLEASE CLAIRFY.
 3) SHT A.13 SHOWS 12" X 6" GUTTER, BUT
 SHT P6 SHOWS THE GUTTER TO BE 16"WX6"D
 PLEASE CLAIRFY.
 4) PROVIDE ELEVATION FOR GUTTER SHOWING
 PITCH TO DOWNSPOUTS, (SLOPE), ON SOUTH
 SIDE OF BLDG.
 5) SHTS A.13 & P6. A.13 SHOWS 9 DOWN-
 SPOUTS ON SOUTH SIDE AND SHT P6 SHOWS
 11 DOWNSPOUTS. PLEASE CLAIRFY
 6) SHT P6 STILL SHOWS URNALS IN MEN'S
 TOILET ROOMS.
 7) SHT P4 REVISION DELETED GASOLINE, OIL
 SANT INTECEPTOR WITH CALCULATIONS AND
 THE SUMP PUMP DETAIL. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS