2003-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTS A-9,A-10,A-24. TRAINING ROOM
 UNISEX TOILET DETAIL AND MEZZANINE LOUN-
 GE. DOOR SHALL NOT OPEN INTO THE CLEAR
 FLOOR SPACE REQUIRED BY ANY FIXTURE.
 SEC 11-4.22.2, 11-4.17.5. 11-4.23.2
 2) ALL PLUMBING APPLIANCES SHALL BE BY
 AN APPROVED AGENCY. SECTION 303.4, AND
 303.4.1
 3) MSDS SHEETS NOT FOUND. NOTIFIED MR.
 HENRY O. TRIMM AND HE INDICATED HE WILL
 SEND SHEETS.
  
 REVIEW BY KEN STEVENS