2004-04-01 00:00:00 | ****CORRECTIONS**** |
| WINDOW/STOREFRONT SHOP DRAWINGS |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE DRAWINGS ARE TO BE REVIEWED BY |
| THE DESIGNER OF RECORD.THE ARCHITECT |
| WHO SPECIFIED THE WIND PRESSURES IS |
| HENRY TRIMM ON SHEET A4.HE ALSO REFERS |
| TO WIND PRESSURES ON THE STRUCTURALS, |
| WHICH WAS DONE BY CAL ENGINEERING. |
| |
| 2.)PRODUCT APPROVALS FOR IMPACT GLASS |
| WERE ALREADY APPROVED AND DO NOT NEED |
| A SECOND APPROVAL.HOWEVER THE PERMIT |
| WAS ISSUED WITH A PROVISO TO SUBMIT |
| LEGIBLE COPIES OF THE NOAS.THE |
| COPIES SUBMITTED ARE NOT LEGIBLE. |
| THE NON-IMPACT PRODUCT APPROVALS ARE A |
| A CHANGE FROM THE ORIGINAL PERMIT PLAN. |
| SUBMIT AS A REVISION FOR REVIEW. |
| |
| 3.)PROVIDE INFORMATION IN REGARDS TO |
| WHERE THE SHUTTERS WILL BE STORED. |
| SHOW THAT THE AREA CAN |
| ACCOMODATE THE SHUTTERS AND INDICATE |
| HOW THEY WILL BE STORED (FLAT OR |
| VERTICALLY).IF THEY ARE STORED |
| VERTICALLY, A RACK DETAIL MUST BE |
| PROVIDED.THIS PERMIT WAS ISSUED WITH |
| A PROVISO TO SUBMIT AN INSTALLATION |
| SCHEDULE.PROVIDE AT THIS TIME. |
| |
| 4.)THE REVIEW NOTE FROM DON COLEMAN, |
| AUTO BUILDERS STATES THAT SHOP DRAWINGS |
| ARE NOT REQUIRED FOR THE INTERIOR |
| WINDOWS.THE PLAN, A1 NOTES A 2HR |
| OCCUPANCY SEPARATION.DOES THIS APPLY |
| TO THESE WINDOWS? |
| |
| 5.)THE PRODUCT APPROVALS SUBMITTED |
| ARE ILLEGIBLE.LEGIBLE COPIES MAY BE |
| AVAILABLE AT WWW.MIAMIDADE.GOV (FIND |
| A DEPARTMENT, BUILDING CODE COMPLIANCE, |
| PRODUCT CONTROL, PRODUCT APPROVAL |
| SEARCH). |
| |
| 6.)THE SITE SPECIFIC PRODUCT APPROVAL |
| FOR THE 181X120 WINDOW MUST BE REVIEWD, |
| SIGNED AND SEALED BY THE DESIGNER OF |
| RECORD IN BOX 10.THE PRINTED NAME, |
| LICENSE NUMBER, FIRM NAME AND AUTH # IF |
| APPLICABLE, ADDRESS IS INFORMATION |
| REQUIRED TO BE ON THIS SHEET FAC61G15- |
| 23.002 (ENGINEERS), FAC61G1-16.003, 004. |
| |
| CC:HAROLD PISKURA |