Plan Review Notes
Plan Review Notes For Permit 03041167
Permit Number 03041167
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) SHTS A.9, A.10, & A.24, IF TOILET
 FACILITIES ARE PROVIDED ON A SITE, THEN
 EACH SUCH PUBLIC OR COMMON USE TOILET
 FACILITY SHALL COMPLY WITH SECTION
 11-4.22.SECTION 11-4.1.3(11)
 2) SHTS A.9, A.10, & A.24, IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST ONE
 SHALL BE A STANDARD STALL COMPLYING WITH
 SEC 11-4.17.SECTION 11-4.22.4
 3) SHT A.14 RELIEF SCUPPER DETAIL,
 PLEASE INDICATE HEIGHT OF FLOW LINE OFF
 ROOF PER SECTION 1503.4.2
 4) SHT A.25 ALL LOUNGE SINKS SHALL COM-
 PLY WITH SECTION 11-4.24 AND ALL SUB-
 SECTIONS.
 5) SHTS P1 & P3 HOSE BIBB SHALL HAVE A
 SHUTOFF VALVE. SECTION 606.2(2)
 6) SHT P-3 PLEASE CONTACT RODNEY COMPO,
 INDUSTRIAL PRE-TREATMENT, ENVIRONMENTAL
 COMPLIANCE FOR SIZING THE OIL INTERCEPT-
 OR. WASTE ORD 2938-96. (561)837-4074.
 7) PLEASE PROVIDE MANUF INFO FOR MYERS
 GRINDER PUMP. PLEASE SHOW LISTING FOR
 PUMP.
 8) SJTS A.13, P4, & P6. SHT A.13 SHOWS
 8 - 8" ROOF DRAINS. 6 AT 14,000 SQ FT &
 2 AT 7,100 SQ FT.-SHTS P4 & P6 SHOWS
 8" ROOF DRAINS (TYPICAL OF 6) & 6" ROOF
 DRAINS (TYPICAL OF 4) ALL AT 7,100 SQ FT
 PLEASE CLAIRFY. - ALSO 14,000 SQ FT ON A
 HORIZONTAL DRAIN REQUIRES MIN. 10" PIPE,
 7,100 SQ FT REQUIRES 8" HORIZONTAL PIPE
 SIZE, & 4,500 SQ FT REQUIRES 6" HORIZON-
 TAL PIPE.
 9) PLEASE PROVIDE A LIST OF STORAGE
 MATERIALS AND MSDS SHEETS FOR ANY HAZ-
 ARDOUS MATERIALS. - AN EMERGENCY EYE
 WASH AND OR SHOWER MAY BE REQUIRED DE-
 PENDING ON MSDS INFORMATION RECIEVED.
 10) SEPARATE IRRIGATION PERMIT & PLANS
 SHALL BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692