Date |
Text |
2003-05-15 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| |
| 1) SHTS A.9, A.10, & A.24, IF TOILET |
| FACILITIES ARE PROVIDED ON A SITE, THEN |
| EACH SUCH PUBLIC OR COMMON USE TOILET |
| FACILITY SHALL COMPLY WITH SECTION |
| 11-4.22.SECTION 11-4.1.3(11) |
| 2) SHTS A.9, A.10, & A.24, IF TOILET |
| STALLS ARE PROVIDED, THEN AT LEAST ONE |
| SHALL BE A STANDARD STALL COMPLYING WITH |
| SEC 11-4.17.SECTION 11-4.22.4 |
| 3) SHT A.14 RELIEF SCUPPER DETAIL, |
| PLEASE INDICATE HEIGHT OF FLOW LINE OFF |
| ROOF PER SECTION 1503.4.2 |
| 4) SHT A.25 ALL LOUNGE SINKS SHALL COM- |
| PLY WITH SECTION 11-4.24 AND ALL SUB- |
| SECTIONS. |
| 5) SHTS P1 & P3 HOSE BIBB SHALL HAVE A |
| SHUTOFF VALVE. SECTION 606.2(2) |
| 6) SHT P-3 PLEASE CONTACT RODNEY COMPO, |
| INDUSTRIAL PRE-TREATMENT, ENVIRONMENTAL |
| COMPLIANCE FOR SIZING THE OIL INTERCEPT- |
| OR. WASTE ORD 2938-96. (561)837-4074. |
| 7) PLEASE PROVIDE MANUF INFO FOR MYERS |
| GRINDER PUMP. PLEASE SHOW LISTING FOR |
| PUMP. |
| 8) SJTS A.13, P4, & P6. SHT A.13 SHOWS |
| 8 - 8" ROOF DRAINS. 6 AT 14,000 SQ FT & |
| 2 AT 7,100 SQ FT.-SHTS P4 & P6 SHOWS |
| 8" ROOF DRAINS (TYPICAL OF 6) & 6" ROOF |
| DRAINS (TYPICAL OF 4) ALL AT 7,100 SQ FT |
| PLEASE CLAIRFY. - ALSO 14,000 SQ FT ON A |
| HORIZONTAL DRAIN REQUIRES MIN. 10" PIPE, |
| 7,100 SQ FT REQUIRES 8" HORIZONTAL PIPE |
| SIZE, & 4,500 SQ FT REQUIRES 6" HORIZON- |
| TAL PIPE. |
| 9) PLEASE PROVIDE A LIST OF STORAGE |
| MATERIALS AND MSDS SHEETS FOR ANY HAZ- |
| ARDOUS MATERIALS. - AN EMERGENCY EYE |
| WASH AND OR SHOWER MAY BE REQUIRED DE- |
| PENDING ON MSDS INFORMATION RECIEVED. |
| 10) SEPARATE IRRIGATION PERMIT & PLANS |
| SHALL BE REQUIRED. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |
| (561) 805-6721 |
| FAX (561) 653-2692 |