Date Text
2003-05-07 00:00:00************* UNSAT*************
  
 1)NOTE: PLEASE VERIFY CODE LETTER
 OF FIRE PUMP MOTOR/OR PLEASE NOTE AS
 "LISTED W/OCP SET FOR LOCKED ROTOR".
 695-4-B1
  
 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 CONTRACTOR TO PROVIDE SIGNAGE FOR MEANS
 OF DISC OF MAINS 1 AND FIRE PUMP/ LOCAT-
 -IONS ETC.230-2E
  
 3)NOTE: PLEASE SEE THAT THERE IS A PANEL
 -BOARD "M" SHOWN ON SCHEDULES, BUT NOTH-
 ING SHOWN ON RISER DIAGRAM? SHOWN ON
 FLOOR PLAN ALSO?
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS
 AT 125%. 220-3,220-10,220-11,220-13,
 215-3,230-42 ETC.
  
 5)NOTE: PLEASE CORRELATE PANEL "A" AND
 RISER, SHOWS FEED TO PANEL "T" W/ #2`S
 AND RISER SHOWS # 1`S?
  
 6)NOTE: PLEASE SEEPANEL"A" ALSO SHOWS
 FEEDING PANEL "M".
  
 7)NOTE: PLEASE SEE PANEL "L", BOXES
 CHECKED FOR MLO& MCB. RISER, SHOWS AS
 MLO. (MISPRINT)
  
 8)NOTE: PLEASE SEE 700-16 FOR FIXTURES
 LOCATED IN SOME AREAS THAT ARE SHOWN
 W/ SINLGE BALLAST(ELEC RMS).
  
 9)NOTE: PLEASE CLARIFY LIGHTING IN AREAS
 /HALLWAYS NEARS PANELS, B>L>M.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]