2003-05-07 00:00:00 | ************* UNSAT************* |
| |
| 1)NOTE: PLEASE VERIFY CODE LETTER |
| OF FIRE PUMP MOTOR/OR PLEASE NOTE AS |
| "LISTED W/OCP SET FOR LOCKED ROTOR". |
| 695-4-B1 |
| |
| 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| CONTRACTOR TO PROVIDE SIGNAGE FOR MEANS |
| OF DISC OF MAINS 1 AND FIRE PUMP/ LOCAT- |
| -IONS ETC.230-2E |
| |
| 3)NOTE: PLEASE SEE THAT THERE IS A PANEL |
| -BOARD "M" SHOWN ON SCHEDULES, BUT NOTH- |
| ING SHOWN ON RISER DIAGRAM? SHOWN ON |
| FLOOR PLAN ALSO? |
| |
| 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE ALSO SHOW ALL CONTINUOUS LOADS |
| AT 125%. 220-3,220-10,220-11,220-13, |
| 215-3,230-42 ETC. |
| |
| 5)NOTE: PLEASE CORRELATE PANEL "A" AND |
| RISER, SHOWS FEED TO PANEL "T" W/ #2`S |
| AND RISER SHOWS # 1`S? |
| |
| 6)NOTE: PLEASE SEEPANEL"A" ALSO SHOWS |
| FEEDING PANEL "M". |
| |
| 7)NOTE: PLEASE SEE PANEL "L", BOXES |
| CHECKED FOR MLO& MCB. RISER, SHOWS AS |
| MLO. (MISPRINT) |
| |
| 8)NOTE: PLEASE SEE 700-16 FOR FIXTURES |
| LOCATED IN SOME AREAS THAT ARE SHOWN |
| W/ SINLGE BALLAST(ELEC RMS). |
| |
| 9)NOTE: PLEASE CLARIFY LIGHTING IN AREAS |
| /HALLWAYS NEARS PANELS, B>L>M. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED |
| SHEETS AND INSERT NEW SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |