2003-05-15 00:00:00THIS BUILDING WILL BE AN H3 OCCUPANCY AS
 DEFINED IN FBC 308.2.1.THE STORAGE OF
 TIRES CONSTITUTES A "FLAMMABLE SOLID"
 AS CALLED OUT IN FBC 308.2.1 AND
 DEFINED IN FBC 202.
  
 THEREFORE THE 100,000 + SQUARE FEET
 BUILDING PROPOSED FAR EXCEEDS THE AREA
 FOR A GROUP H BUILDING IN FBC TABLE
 500.FURTHER, FOOTNOTE C TO TABLE 500
 PROHIBITS AREA AND/OR HEIGHT INCREASES.