2003-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-3 DETAIL #9 SCUPPER DETAIL,
 PLEASE INDICATE THE HEIGHT OF THE
 OPENING FOR THE SCUPPER.
 2) SHT A-3 PLEASE PROVIDE CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS,
 (SCUPPERS). PLEASE SHOW 1/2 AREA OF ALL
 VERTICAL WALLS IN CALCS. AND TOTAL ROOF
 AREA DRAINED. SECTION 1106 & 1107
 3) SHT P-1 NOTES #7 & 26, P/T LINE SHALL
 NOT RUN UNDERGROUND THEN RISE UP 6"
 ABOVE GRADE. THIS WILL TRAP THE RELIEF
 LINE. SEC 504.7.1
 4) SHT P-4 THERMAL EXPANSION CONTROL IS
 REQUIRED. SECTION 607.3.2
 5) SHTS P-1 & P-5 (SANT. RISER DIAGRAM)
 MINIMUM DISTANCE FOR CLEANOUTS IS 100'.
 SEC 708.3.1. CLEANOUTS SHALL BE INSTALL-
 ED AT EACH CHANGE OF DIRECTION GREATER
 THAN 45 DEGREES. SECTION 708.3.3
 6) SHT P-5 WATER RISER DIAGRAM, AIR
 CHAMBERS NOT APPROVED. WATER HAMMER
 ARRESTORS REQUIRED BY 604.9 SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT IN THE CEILING. PDI-WH
 201 AND MANUF INSTALLATION INSTRUCTIONS.
 7) SHT P-6 PLUMBING SPECIFICATIONS,
 #3 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE REFERENCE.
 #11 2-1/2" PIPE AND SMALLER SHALL BE
 SLOPED AT 1/4" PER FOOT. TABLE 704.1
 8) SITE ENGINEERING PLANS REFER TO IRRI-
 GATION PLANS. PLANS NOT FOUND. SEPARATE
 PERMIT - PLANS FOR IRRIGATION REQUIRED.
  