2003-05-15 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT A-3 DETAIL #9 SCUPPER DETAIL, |
| PLEASE INDICATE THE HEIGHT OF THE |
| OPENING FOR THE SCUPPER. |
| 2) SHT A-3 PLEASE PROVIDE CALCULATIONS |
| FOR PRIMARY AND SECONDARY ROOF DRAINS, |
| (SCUPPERS). PLEASE SHOW 1/2 AREA OF ALL |
| VERTICAL WALLS IN CALCS. AND TOTAL ROOF |
| AREA DRAINED. SECTION 1106 & 1107 |
| 3) SHT P-1 NOTES #7 & 26, P/T LINE SHALL |
| NOT RUN UNDERGROUND THEN RISE UP 6" |
| ABOVE GRADE. THIS WILL TRAP THE RELIEF |
| LINE. SEC 504.7.1 |
| 4) SHT P-4 THERMAL EXPANSION CONTROL IS |
| REQUIRED. SECTION 607.3.2 |
| 5) SHTS P-1 & P-5 (SANT. RISER DIAGRAM) |
| MINIMUM DISTANCE FOR CLEANOUTS IS 100'. |
| SEC 708.3.1. CLEANOUTS SHALL BE INSTALL- |
| ED AT EACH CHANGE OF DIRECTION GREATER |
| THAN 45 DEGREES. SECTION 708.3.3 |
| 6) SHT P-5 WATER RISER DIAGRAM, AIR |
| CHAMBERS NOT APPROVED. WATER HAMMER |
| ARRESTORS REQUIRED BY 604.9 SHALL BE |
| LOCATED NEAR THE FIXTURE IN AN "EFFECT- |
| IVE RANGE" NOT IN THE CEILING. PDI-WH |
| 201 AND MANUF INSTALLATION INSTRUCTIONS. |
| 7) SHT P-6 PLUMBING SPECIFICATIONS, |
| #3 AIR CHAMBERS ARE NOT APPROVED. PLEASE |
| DELETE REFERENCE. |
| #11 2-1/2" PIPE AND SMALLER SHALL BE |
| SLOPED AT 1/4" PER FOOT. TABLE 704.1 |
| 8) SITE ENGINEERING PLANS REFER TO IRRI- |
| GATION PLANS. PLANS NOT FOUND. SEPARATE |
| PERMIT - PLANS FOR IRRIGATION REQUIRED. |
| |
| REVIEW BY KEN STEVENS |