Plan Review Notes
Plan Review Notes For Permit 03041050
Permit Number 03041050
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-02 00:00:00THIS BUILDING WILL REQUIRE A RESIDENT
 INSPECTOR AS PROVIDED FOR IN FBC 105.3
 AS AMENDED BY THE CITY OF WEST PALM
 BEACH. PLEASE CONTACT DON NEELY AT
 561-805-6665 FOR MORE INFORMATION.
  
 STAIR #1 DOES NOT COMPLY WITH FBC 1010.1
 SEE ALSO FBC 1010.3 #1.
  
 THE FOAM TRIM SHOWN AT THE TO OF THE
 PARAPET WALLS ON SHEET A7 AND ELSEWHERE
 DOES NOT COMPLY WITH FBC 1404.1.1.
  
 PLEASE PROVIDE SPECIFIC CONSTRUCTION
 DETAILS FOR THE LOBBY SOFFIT AND
 SIMILAR AS SHOWN ON SHEET A-11 "FASTEN
 TO THE STRUCTURE ABOVE"SEE FBC 104.2.
  
 SHEET S1 CALLS FOR A SOIL BEARING VALUE
 4 KSF AND THE ALTERRA E&T REPORT IS
 RECOMMENDING 2.5 KSF.PLEASE CLARIFY.
  
 IF TEST AND/OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE DOORS, WINDOWS AND ROOF
 COVERING ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, A SEPARATE PERMIT
 AND FEES WILL BE REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.