Plan Review Notes For Permit 03040978 |
Permit Number |
03040978 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-05-01 00:00:00 | ************ UNSAT ***************** | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | REVIEW. NO CORRECTIONS WERE MADE. | | | | 2)NOTE: PLEASE SUBMIT AND MEET NEC . | | THERE ARE MANY ITEMS THAT NEED TO MEET | | 225-31/230-72/250-122//215-5 ETC. | | | | 3)NOTE: PLEASE SEE ATTACHED LETTER FOR | | FS 553.80(2)(B). PLEASE NOTE, PLANS | | FOR THREE REVIEW AND SAME COMMENTS SHALL | | BE ASSESSED A FOUR TIME FEE FOR PLAN | | REVIEW PORTION OF PERMIT FEE.(30%) OF | | PERMIT FEE X-FOUR. | | | | PLEASE SEE ABOVE COMMENT AND COMMENTS | | FROM FIRST REVIEW. IF THERE ARE ANY | | QUESTIONS,PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|