Plan Review Notes
Plan Review Notes For Permit 03040978
Permit Number 03040978
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-22 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND RISER DIAGRAM.
 SHOWS NEW 60A FEED TO GARAGE AND YET
 RISER SHOWS 3-3/0` FROM METER???
  
 2)NOTE: PLEASE ALSO SEE NEW LIGHTING
 BEING FED FROM EXIST PANEL ALSO???
  
 PLEASE NOTE, TWO COMPLETELY WAYS OF
 FEEDING GARAGE IS BEING SHOWN AND CAN
 GERERATE TWO SETS OF NOTES FOR WHAT IS
 SHOWN.
 PLEASE SEE 225-31/230-72 FOR SOME REQ`-
 -MENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372