Plan Review Notes
Plan Review Notes For Permit 03040961
Permit Number 03040961
Review Stop P
Sequence Number 2
Notes
Date Text
2003-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) FROM PREVIOUS REVIEW:
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 **(SEE ATTACHED SHEET FOR SAMPLE OF DE-
 TAIL FOR ADDRESSING COMMENTS #'S 1 & 2)
 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 ***(SEE ATTACHED SHEET FOR EXAMPLE OF
 POOL EQUIP. ANCHORING SLAB.)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) ALL SHEETS OF A SIGNED AND SEALED
 ENGINEERED SET OF PLANS SHALL BE SIGNED
 AND SEALED BY THE ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692