2003-04-16 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. (DETAIL) |
| 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| MENT AVOIDANCE. (DETAIL) |
| 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO |
| SUCTION INLETS SHALL BE PROVIDED FOR EA |
| PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| OR LOCATED ON TWO DIFFERENT PLANES. |
| (DETAIL)- PIPING SCHEMATIC ON SHT #1 |
| OF 5 SHOWS TWO WALL DRAINS. POOL PIPING |
| LAYOUT SHOW ONE FLOOR MAIN DRAIN AND ONE |
| WALL MAIN DRAIN. PLEASE CLAIRFY. |
| 4) SHT 1 0F 5 - NO SPA PIPING SHOWN ON |
| SCHEMATIC. PLEASE REVISE AND RESUBMIT |
| SCHEMATIC. ALSO SHOW BLOWER, SPA JET RE- |
| TURN ECT. |
| 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| BASE IN A MANNER THAT WILL ELIMINATE |
| STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| AL 4" THICK. (DETAIL) |
| 6) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 7) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 8) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 9) ALL SHEETS OF A SIGNED AND SEALED |
| ENGINEERED SET OF PLANS SHALL BE SIGNED |
| AND SEALED BY THE ENGINEER OF RECORD. |
| MANUF. INFO. NOT INCLUDED. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |
| (561) 805-6721 |
| FAX (561) 653-2692 |