Plan Review Notes For Permit 03040924 |
Permit Number |
03040924 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-23 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE CORRECT THE FOLLOWING ITEMS ON | | THE PLAN AND RESUBMIT FOR REVIEW. | | | | 1} THE #2 FEEDERS TO PANEL "A" ARE | | INCORRECT FOR A 200AMP OCP. | | | | 2} THE GEC MUST COMPLY WITH 250-24(A)(1) | | AND NOT BE INSTALLED PAST THE FIRST | | MEANS OF DISCONNECT. | | | | 3} THE FEEDER SIZE TO PANEL "B" ON RISER | | DIAGRAM AND ON THE PANEL SCHEDULE ARE | | NOT THE SAME,PLEASE CORRELATE. | | | | 4} THE CALCULATION FOR PANEL "B" ON | | PANEL "A" SCHEDULE AND ON PANEL "B" | | SCHEDULE DO NOT CORRELATE. | | | | 5} THERE IS NO LOAD GIVEN FOR THE | | GARBAGE DISPOSAL IN THE CALCS,PLEASE | | INCLUDE SAME AND CORRECT THE CALCS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|