Plan Review Notes
Plan Review Notes For Permit 03040924
Permit Number 03040924
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING ITEMS ON
 THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} THE #2 FEEDERS TO PANEL "A" ARE
 INCORRECT FOR A 200AMP OCP.
  
 2} THE GEC MUST COMPLY WITH 250-24(A)(1)
 AND NOT BE INSTALLED PAST THE FIRST
 MEANS OF DISCONNECT.
  
 3} THE FEEDER SIZE TO PANEL "B" ON RISER
 DIAGRAM AND ON THE PANEL SCHEDULE ARE
 NOT THE SAME,PLEASE CORRELATE.
  
 4} THE CALCULATION FOR PANEL "B" ON
 PANEL "A" SCHEDULE AND ON PANEL "B"
 SCHEDULE DO NOT CORRELATE.
  
 5} THERE IS NO LOAD GIVEN FOR THE
 GARBAGE DISPOSAL IN THE CALCS,PLEASE
 INCLUDE SAME AND CORRECT THE CALCS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718