2003-05-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-RESUBMIT STORM SHUTTERS INFORMATION | | WITH UPDATED SBCCI PRODUCT APPROVAL | | THAT MATCHES ENGINEERED DRAWINGS. | | 2-REVISE DETAIL S-21 FOR COLUMN BETWEEN | | GARAGE AND STAIRWAY TO MATCH CONDITION | | SHOWN ON 2ND FLOOR FRAMING PLAN. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 3-ROOF FRAMING PLAN: REVISE CONNECTOR | | TC-1 FOR FRAMED WALL. NEED WOOD TO | | WOOD CONNECTOR. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 4-WINDOW 34SH DOESN'T PROVIDE THE 24" | | CLEAR HEIGHT AS REQUIRED BY SECTION | | 1005.4 FBC 2001. REVISE AS REQUIRED. |
|