2003-05-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RESUBMIT STORM SHUTTERS INFORMATION
 WITH UPDATED SBCCI PRODUCT APPROVAL
 THAT MATCHES ENGINEERED DRAWINGS.
 2-REVISE DETAIL S-21 FOR COLUMN BETWEEN
 GARAGE AND STAIRWAY TO MATCH CONDITION
 SHOWN ON 2ND FLOOR FRAMING PLAN. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-ROOF FRAMING PLAN: REVISE CONNECTOR
 TC-1 FOR FRAMED WALL. NEED WOOD TO
 WOOD CONNECTOR. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-WINDOW 34SH DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT AS REQUIRED BY SECTION
 1005.4 FBC 2001. REVISE AS REQUIRED.