Plan Review Notes For Permit 03040845 |
Permit Number |
03040845 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-12-05 00:00:00 | DENIED: | | PLAN SHEET M-202 STAIR 5 INDICATES DUCT | | PENETRATING STAIRWELL AREA.PLEASE | | CLARIFY, PLAN SHEET A-2.1 INDICATES THE | | STAIRWELL HAS A 2 HR FIRE SEPARATION. | | AS PER 2001 FBC 1006.1.3.1 PENETRATIONS | | THROUGH A STARIWAY ENCLOSURE ARE | | PROHIBITED UNLESS IT IS FOR STAIRWELL | | PRESSURIZATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|