Plan Review Notes
Plan Review Notes For Permit 03040756
Permit Number 03040756
Review Stop P
Sequence Number 6
Notes
Date Text
2004-02-05 00:00:00REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS AP/P14.01 & AP/P14.03 CLEANOUTS
 REQUIRED PER SECTIONS 708.3.1 & 708.3.3.
 2) SHT AP/14.06 CLEANOUTS REQUIRED PER
 SECTION 708.3.1 & 708.3.3.
 3) SHT AP/P14.08 DETAIL #3 SHOWS THE
 DRAIN LINE FOR THE EMERGENCY SAFETY PAN
 FOR THE WATER HEATER DELETED, AND THE
 RELIEF LINE, (T&P), DRAINING OUTSIDE.
 DETAIL #2 SHOWS T&P LINE DISCHARGING IN-
 TO THE SAFETY PAN FOR THE WATER HEATER.
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]