Plan Review Notes
Plan Review Notes For Permit 03040756
Permit Number 03040756
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-24 00:00:00DENIED
  
 1) FROM PREVIOUS REVIEW. CLEANOUTS RE-
 QUIRED IN BOTH BREEZWAYS, (STAIRWAYS),
 SHTS P-14.01 & P-14.03. CLEANOUTS SHALL
 BE FLOOR CLEANOUTS AS THEY ARE REQUIRED
 TO BE TWO WAY CLEANOUTS, OR MORE CLEAN-
 OUTS WILL BE REQUIRED ANT THE UPSTREAM
 END OF THE BLDG DRAIN. 708.5 CLEANOUTS
 ARE REQUIRED TO BE ACCESSIBLE SO THEY
 SHALL BE LOCATED OUTSIDE OF THE UNITS.
 708.10.
 2) SHT P14.07 WATER RISER DIAGRAMS. IF
 WATER HAMMER ARRESTORS ARE INSTALLED AT
 THE WATER HEATERS THEY SHALL BE LOCATED
 AS REQUIRED FOR ALL OTHER WATER HAMMER
 ARRESTORS. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.
 3) SUBMIT A HORIZONTAL SANITARY RISER
 DIAGRAM. SHOW ALL RISER TIE-INS AND
 SHOW DRAINAGE FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692