Plan Review Notes For Permit 03040756 |
Permit Number |
03040756 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-24 00:00:00 | DENIED | | | | 1) FROM PREVIOUS REVIEW. CLEANOUTS RE- | | QUIRED IN BOTH BREEZWAYS, (STAIRWAYS), | | SHTS P-14.01 & P-14.03. CLEANOUTS SHALL | | BE FLOOR CLEANOUTS AS THEY ARE REQUIRED | | TO BE TWO WAY CLEANOUTS, OR MORE CLEAN- | | OUTS WILL BE REQUIRED ANT THE UPSTREAM | | END OF THE BLDG DRAIN. 708.5 CLEANOUTS | | ARE REQUIRED TO BE ACCESSIBLE SO THEY | | SHALL BE LOCATED OUTSIDE OF THE UNITS. | | 708.10. | | 2) SHT P14.07 WATER RISER DIAGRAMS. IF | | WATER HAMMER ARRESTORS ARE INSTALLED AT | | THE WATER HEATERS THEY SHALL BE LOCATED | | AS REQUIRED FOR ALL OTHER WATER HAMMER | | ARRESTORS. PDI-WH 201 & MANUF. INSTALL. | | INSTRUCTIONS. | | 3) SUBMIT A HORIZONTAL SANITARY RISER | | DIAGRAM. SHOW ALL RISER TIE-INS AND | | SHOW DRAINAGE FIXTURE UNITS AS THEY | | ACCUMULATE IN THE SYSTEM. 104.2.1 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|