Plan Review Notes
Plan Review Notes For Permit 03040756
Permit Number 03040756
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-09-04 00:00:00APPROVED PROVISO:
  
 1) ELECTRONIC SWITCHES ARE REQUIRED
 ON THE BACKFLOW DEVICE FOR FIRE
 SERVICE.
  
 2) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 3) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING IS THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 4) THE FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE
 SINCE PERMITS WILL BE RECEIVED AFTER
 THE AUGUST 1, 2003 EFFECTIVE DATE.
  
 5) NFPA 13R SYSTEMS ARE NOT ALLOWED
 FOR 5 STORY BUILDINGS.
  
 6) WAFER CHECK VALVES ON THE SUPPLY
 SIDE OF A FIRE PUMP CANNOT BE INSTALLED
 SO CLOSE TO THE PUMP.
  
 7) FINAL EASEMENTS WITH REGARDS TO
 FIRE LINES AND UTILITIES HAVE NOT
 YET BEEN WORKED OUT. ALL APPROVALS
 MUST BE OBTAINED FROM THE PROPER
 AUTHORITIES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910