Date Text
2003-06-24 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE SEE THAT THERE ARE STILL
 SOMERECEPTS MISSING FOR 2' OF WALL
 SPACE.210-52
  
 2)NOTE: PLANS/RISER SHOW 3 PARALLEL RUNS
 OF UNGROUNDED CONDUCTORS, HOWEVER ONLY
 SHOWS TWO PARALLEL RUNS OF GROUNDED
 CONDUCTORS? DUE TO INDUCTIONAND INDUCT-
 -IVE HEATING, A 3RD RUN OF THE GROUNDED
 (NEUTRAL) CONDUCTOR WILL BE REQ`D.
 300-20/310-4
 THIS WOULD NOT BE REQ`D FOR BLDG 1, SERV
 -#4.
  
 3)NOTE: PLEASE SEE 250-24, NOTE ON RISER
 DIAGRAM FOR CLUBHOUSE MENTIONS, TO BOND
 GROUND AND NEUTRAL TOGETHER, THIS DONE
 AT THE FIRST MEANS OF DISC, AS PER
 250-24
  
 4)NOTE: PLEASE SEE THAT THERE IS NOT
 ENOUGH INFORMATION FOR FIRE PUMP,
 FIRE PUMP VOLTAGE, MEANS OF DISC, CODE
 LETTER, SIZING OF DISC MEANS FOR LOCKED
 ROTOR, RISER DIAGRAM ETC.430-150,430-151
 (B), 695-4B-1,2 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE OTHER REVIEWS, THAT MAY HAVE
 AN AFFECT ON ELECTRICAL PLANS.
  