Plan Review Notes
Plan Review Notes For Permit 03040756
Permit Number 03040756
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34"
 MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE
 DETAIL PAGE 7.52 DESIGN MANUAL.
 2) SHT A5.02 - 11-4.16.5 FLUSH CONTROLS
 SHALL BE MOUNTED ON THE WIDE SIDE OF
 TOILET AREAS. (AWAY FROM SIDE GRAB BARS)
 3) SEPARATE POOL PERMIT REQUIRED. HEALTH
 DEPT. PLAN REVIEW REQUIRED FOR FACILIT-
 IES.
 3) SEPARATE IRRIGATION PERMIT REQUIRED.
 4) SHT P14.03 CLEANOUTS REQUIRED IN BOTH
 BREEZEWAYS. SECTION 708.3.1 (MAX 100')
 5) ALL UNITS - PLEASE SPECIFY EITHER
 SPECIFICATION "A" OR "B" BATHROOMS AS
 REQUIRED BY DESIGN MANUAL REQUIREMENT
 7B, PAGE 7.35.
 6) SHT P14.07 WATER RISER DIAGRAMS, THE
 WATER HAMMER ARRESTORS REQUIRED IN SEC.
 604.9, (ICE MAKER, DISHWASHER, WASH
 MACHINE), SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 7) SHT P14.06 RISERS S4 & S5, THE WASTE
 STACK SHALL BE THE SAME SIZE THROUGHOUT
 THE LENGTH OF THE WASTE STACK. SECTION
 910.4
 8) RPZ BACKFLOW REQUIRED IN WATER SERV.
 AT EACH BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692