Date |
Text |
2003-04-30 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FHA-AMEND 98 DESIGN MANUAL |
| |
| 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34" |
| MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE |
| DETAIL PAGE 7.52 DESIGN MANUAL. |
| 2) SHT A5.02 - 11-4.16.5 FLUSH CONTROLS |
| SHALL BE MOUNTED ON THE WIDE SIDE OF |
| TOILET AREAS. (AWAY FROM SIDE GRAB BARS) |
| 3) SEPARATE POOL PERMIT REQUIRED. HEALTH |
| DEPT. PLAN REVIEW REQUIRED FOR FACILIT- |
| IES. |
| 3) SEPARATE IRRIGATION PERMIT REQUIRED. |
| 4) SHT P14.03 CLEANOUTS REQUIRED IN BOTH |
| BREEZEWAYS. SECTION 708.3.1 (MAX 100') |
| 5) ALL UNITS - PLEASE SPECIFY EITHER |
| SPECIFICATION "A" OR "B" BATHROOMS AS |
| REQUIRED BY DESIGN MANUAL REQUIREMENT |
| 7B, PAGE 7.35. |
| 6) SHT P14.07 WATER RISER DIAGRAMS, THE |
| WATER HAMMER ARRESTORS REQUIRED IN SEC. |
| 604.9, (ICE MAKER, DISHWASHER, WASH |
| MACHINE), SHALL BE LOCATED NEAR THE FIX- |
| TURE IN AN "EFFECTIVE RANGE" NOT IN THE |
| CEILING AS SHOWN. PDI-WH 201 AND MANUF. |
| INSTALLATION INSTRUCTIONS. |
| 7) SHT P14.06 RISERS S4 & S5, THE WASTE |
| STACK SHALL BE THE SAME SIZE THROUGHOUT |
| THE LENGTH OF THE WASTE STACK. SECTION |
| 910.4 |
| 8) RPZ BACKFLOW REQUIRED IN WATER SERV. |
| AT EACH BLDG. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |
| (561) 805-6721 |
| FAX (561) 653-2692 |