Plan Review Notes
Plan Review Notes For Permit 03040756
Permit Number 03040756
Review Stop M
Sequence Number 1
Notes
Date Text
2003-06-24 00:00:00TYPE II BUILDING:
 PLEASE CLARIFY VENTILATION REQUIREMENTS
 FOR THE CORRIDORS AS PER 2001 FBC(M)
 TABLE 403.3, PUBLIC SPACES - CORRIDORS
 .05 CFM PER SQ FT.
  
 CLUBHOUSE:
 COMMENT #3 FROM PREVIOUS REVIEW, DRYERS
 THAT EXHAUST GREATER THAN (SHOULD READ
 200 CFM NOT 2,000 CFM) SHALL BE PROVIDED
 WITH MAKE UP AIR.
  
 PLEASE NOTE, THE WALL SEPARATING THE
 FIRE PUMP RM & LAUNDRY RM HAS A 1 HR
 FIRE RESISTANT RATING.(FIRE DAMPERS
 ARE NOT PERMITTED IN DRYER EXHAUST).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.