Plan Review Notes For Permit 03040756 |
Permit Number |
03040756 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-24 00:00:00 | TYPE II BUILDING: | | PLEASE CLARIFY VENTILATION REQUIREMENTS | | FOR THE CORRIDORS AS PER 2001 FBC(M) | | TABLE 403.3, PUBLIC SPACES - CORRIDORS | | .05 CFM PER SQ FT. | | | | CLUBHOUSE: | | COMMENT #3 FROM PREVIOUS REVIEW, DRYERS | | THAT EXHAUST GREATER THAN (SHOULD READ | | 200 CFM NOT 2,000 CFM) SHALL BE PROVIDED | | WITH MAKE UP AIR. | | | | PLEASE NOTE, THE WALL SEPARATING THE | | FIRE PUMP RM & LAUNDRY RM HAS A 1 HR | | FIRE RESISTANT RATING.(FIRE DAMPERS | | ARE NOT PERMITTED IN DRYER EXHAUST). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|