2003-04-29 00:00:00 | *********** UNSAT ***************** |
| |
| 1)NOTE: PLEASE CLARIFY DISTANCE FOR |
| VOLTAGE DROP ON SITE LIGHTING. |
| WE ARE UNDER 2002FBC. PLEASE SEE WIND |
| LOAD REQ`D FOR POLES. NOTES 120MPH. |
| |
| 2)NOTE: PLEASE PLACE NOTE/REQUIREMENTS |
| ON PLAN FOR FHAC 24 CFR 100.205. |
| |
| 3)NOTE: PLEASE SEE PLANS FOR RECEPT |
| SPACING. SOME MISSING PER 210-52. |
| 2' OF WALL SPACE. |
| |
| 4)NOTE: PLEASE NOTE, SD`S ARE TO BE A |
| MIN OF 3' FROM BATH DOOR AND KITCHEN. |
| |
| 5)NOTE: PLEASE CLARIFY ALL SERVICE |
| ENTRANCE CONDUCTORS SIZE AND # OF PARA- |
| -LLEL RUNS. PLEASE SEE 240-3 B&C |
| 110-14 AND 310-16 |
| |
| 6)NOTE: PLEASE CLARIFY WATER HEATER LOAD |
| SHOWN AT 11800W? |
| PLEASE CORRELATE W/ PANEL SCHEDULE. |
| SHOWN BEING DIFFERENT. |
| |
| 7)NOTE: PLEASE SEE E-16.09 NOTE AT |
| BOTTOM OF PANELS MENTIONS : SEE EXX FOR |
| LOADS. PLEAS FILL IN APPROPRIATE PAGE. |
| |
| 8)NOTE: PLEASE SEE LIST/CLARIFY THE |
| REQ`D ARC FAULT PROTECTED CIRCUITS PER |
| 210-12 |
| |
| 9)NOTE: PLEASE PANEL C2, SHOWS LOCATION |
| TO BE IN UTILITY ROOM. PLEASE SEE FLOOR |
| PLAN, SHOWN IN HALL? PLEASE CORRELATE. |
| |
| 10)NOTE: PLEASE CORRELATE LOAD SHOWN FOR |
| WASHER. PANEL SHOWS AS 1.0KW AND LOAD |
| CALCS SHOWS AS 1.5KW(REQ`D) 220-16B |
| |
| 11)NOTE: PLEASE SEE MAIN GROUNDING |
| ELECTRODE REQ`D TO FOOTER STEEL 250-50/ |
| SIZED PER 250-66 SHOWN AS #4/#6 AND #2 |
| FOR ALL OTHERS AND BONDING? |
| |
| 12)NOTE: PLEASE CLARIFY MAINS SHOWN AS |
| "SHUNT TRIP". PLEASE CLARIFY IF THERE |
| IS STILL A MANUAL MEANS OF DISCAND |
| RATED FOR SERVICE. 230-76-230-79 |
| PLEASE NOTE, SHUNT TRIPS ARE NOT RATED |
| FOR MEANS OF DISC. |
| |
| 13)NOTE: PLEASE NOTE, PLANS AND RISER |
| MENTIONS ALUM CONDUCTORS FOR GROUNDING |
| AND BONDING. PLEASE NOTE, PER LOCAL |
| AMENDMENTS TO FBC/NEC AS ADOPTED BY THE |
| CITY OF WEST PALM BEACH, ART 250-62/ |
| 310-2. |
| PLEASE ALSO ADJUST EQUIPMENT GROUNDING |
| TO APT UNITS. PLEASE NOTE, MIXING OF |
| CONDUCTOR AND OR DISSIMILAR METALS. |
| |
| 14)NOTE: PLEASE SEE APPLICATION, MENTION |
| -S CLUBHOUSE UNDER THIS #. PLEASE NOTE, |
| WILL BE SEPARATED UNDER SEPARATE PERMIT |
| AND IS ONLY REVIEW UNDER THIS PERMIT # |
| AT THIS TIME. |
| |
| 15)NOTE: PLEASE CLARIFY AND PROVIDE |
| MORE INFORMATION ON FIRE PUMP SHOWN IN |
| CLUBHOUSE? A COMPLETE REVIEW CAN NOT BE |
| DONE AT THIS TIME FOR THIS.SPECS ETC |
| |
| 16)NOTE: PLEASE SEE LOCATION OF PANEL |
| "LPA" SHOWN IN LIBARY. PLEASE CHANGE |
| LOCATION DUE TO PROXIMITY OF EASILY |
| IGNITABLE MATERIALS.384-7 |
| |
| 17)NOTE: PLEASE PROVIDE GROUNDING |
| ELECTRODE CONDUCTOR SIZES FOR CLUBHOUSE, |
| NOTES MENTIONS SEE RISER, RISER SAYS |
| SEE GROUNDING DETAIL? PLEASE SHOW AND |
| CORRELATE. |
| |
| PLEASE NOTE: THERE MAY BE FURTHER |
| COMMENTS DUE TO SOME ITEMS NOT BEING |
| COMPLETE AT THIS TIME. |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| PLEASE ALSO SEE FIRE REVIEW COMMENTS |
| THAT MAY AFFECT ELECTRICAL PLANS. |
| |