Plan Review Notes
Plan Review Notes For Permit 03040756
Permit Number 03040756
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-29 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY DISTANCE FOR
 VOLTAGE DROP ON SITE LIGHTING.
 WE ARE UNDER 2002FBC. PLEASE SEE WIND
 LOAD REQ`D FOR POLES. NOTES 120MPH.
  
 2)NOTE: PLEASE PLACE NOTE/REQUIREMENTS
 ON PLAN FOR FHAC 24 CFR 100.205.
  
 3)NOTE: PLEASE SEE PLANS FOR RECEPT
 SPACING. SOME MISSING PER 210-52.
 2' OF WALL SPACE.
  
 4)NOTE: PLEASE NOTE, SD`S ARE TO BE A
 MIN OF 3' FROM BATH DOOR AND KITCHEN.
  
 5)NOTE: PLEASE CLARIFY ALL SERVICE
 ENTRANCE CONDUCTORS SIZE AND # OF PARA-
 -LLEL RUNS. PLEASE SEE 240-3 B&C
 110-14 AND 310-16
  
 6)NOTE: PLEASE CLARIFY WATER HEATER LOAD
 SHOWN AT 11800W?
 PLEASE CORRELATE W/ PANEL SCHEDULE.
 SHOWN BEING DIFFERENT.
  
 7)NOTE: PLEASE SEE E-16.09 NOTE AT
 BOTTOM OF PANELS MENTIONS : SEE EXX FOR
 LOADS. PLEAS FILL IN APPROPRIATE PAGE.
  
 8)NOTE: PLEASE SEE LIST/CLARIFY THE
 REQ`D ARC FAULT PROTECTED CIRCUITS PER
 210-12
  
 9)NOTE: PLEASE PANEL C2, SHOWS LOCATION
 TO BE IN UTILITY ROOM. PLEASE SEE FLOOR
 PLAN, SHOWN IN HALL? PLEASE CORRELATE.
  
 10)NOTE: PLEASE CORRELATE LOAD SHOWN FOR
 WASHER. PANEL SHOWS AS 1.0KW AND LOAD
 CALCS SHOWS AS 1.5KW(REQ`D) 220-16B
  
 11)NOTE: PLEASE SEE MAIN GROUNDING
 ELECTRODE REQ`D TO FOOTER STEEL 250-50/
 SIZED PER 250-66 SHOWN AS #4/#6 AND #2
 FOR ALL OTHERS AND BONDING?
  
 12)NOTE: PLEASE CLARIFY MAINS SHOWN AS
 "SHUNT TRIP". PLEASE CLARIFY IF THERE
 IS STILL A MANUAL MEANS OF DISCAND
 RATED FOR SERVICE. 230-76-230-79
 PLEASE NOTE, SHUNT TRIPS ARE NOT RATED
 FOR MEANS OF DISC.
  
 13)NOTE: PLEASE NOTE, PLANS AND RISER
 MENTIONS ALUM CONDUCTORS FOR GROUNDING
 AND BONDING. PLEASE NOTE, PER LOCAL
 AMENDMENTS TO FBC/NEC AS ADOPTED BY THE
 CITY OF WEST PALM BEACH, ART 250-62/
 310-2.
 PLEASE ALSO ADJUST EQUIPMENT GROUNDING
 TO APT UNITS. PLEASE NOTE, MIXING OF
 CONDUCTOR AND OR DISSIMILAR METALS.
  
 14)NOTE: PLEASE SEE APPLICATION, MENTION
 -S CLUBHOUSE UNDER THIS #. PLEASE NOTE,
 WILL BE SEPARATED UNDER SEPARATE PERMIT
 AND IS ONLY REVIEW UNDER THIS PERMIT #
 AT THIS TIME.
  
 15)NOTE: PLEASE CLARIFY AND PROVIDE
 MORE INFORMATION ON FIRE PUMP SHOWN IN
 CLUBHOUSE? A COMPLETE REVIEW CAN NOT BE
 DONE AT THIS TIME FOR THIS.SPECS ETC
  
 16)NOTE: PLEASE SEE LOCATION OF PANEL
 "LPA" SHOWN IN LIBARY. PLEASE CHANGE
 LOCATION DUE TO PROXIMITY OF EASILY
 IGNITABLE MATERIALS.384-7
  
 17)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE CONDUCTOR SIZES FOR CLUBHOUSE,
 NOTES MENTIONS SEE RISER, RISER SAYS
 SEE GROUNDING DETAIL? PLEASE SHOW AND
 CORRELATE.
  
 PLEASE NOTE: THERE MAY BE FURTHER
 COMMENTS DUE TO SOME ITEMS NOT BEING
 COMPLETE AT THIS TIME.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE ALSO SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW