2003-12-22 00:00:00PASSED BY H. PISKURA ON 9/4/03 SEE BELOW
2003-09-04 00:00:00PROVISO:
  
 THE GENERAL NOTES ON THE FIRE
 PROTECTIONPLANS, SHEET FP 13.01 HAVE
 SEVERAL REFERENCES TO NFPA 13R FOR THE
 DESIGN STANDARD.THIS DESIGN MUST BE
 AN NFPA 13 DESIGN IN ITS ENTIRETY IN
 ACCORDANCE WITH FBC 903.2.
  
 ALSO THE FLORIDA BUILDING CODE INVOKES
 NFPA 13-99 NOT THE 2000 EDITION
 DECLARED.PLEASE REVISE AS NECESSARY
 AND ENSURE COMPLIANCE WITH THE 1999
 EDITION.
  
 SHEET FP 13.02 SHOWS A 6" WAFER CHECK
 VALVE ON THE SUCTION SIDE OF THE PUMP
 WITHIN TEN PIPE DIAMETERS OF THE FLANGE.
 SEE NFPA 20-99 SECTION 2-21.3.
  
 SEE NFPA 13-99 CHAPTER 8 FOR DESIGN
 PLAN AND CALCULATION CRITERIA.