Plan Review Notes
Plan Review Notes For Permit 03040755
Permit Number 03040755
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW. CLEANOUTS RE-
 QUIRED IN BOTH BREEZWAYS, (STAIRWAYS),
 SHTS P14.01 & P14.03. CLEANOUTS SHALL BE
 FLOOR CLEANOUTS AS THEY ARE REQUIRED TO
 BE TWO WAY CLEANOUTS, OR MORE CLEANOUTS
 WILL BE REQUIRED AT THE UPSTREAM END OF
 THE BLDG DRAIN. 708.5. CLEANOUTS ARE
 REQUIRED TO BE ACCESSIBLE SO THEY SHALL
 BE LOCATED OUTSIDE OF THE UNITS. 708.10
 2) SHT P14.07 WATER RISER DIAGRAMS. IF
 WATER HAMMER ARRESTORS ARE INSTALLED AT
 THE WATER HEATERS THEY SHALL BE LOCATED
 AS REQUIRED FOR ALL OTHER WATER HAMMER
 ARRESTORS. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.
 3) SUBMIT A HORIZONTAL SANITARY RISER
 DIAGRAM. SHOW ALL RISER TIE-INS AND
 SHOW DRAINAGE FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692