Plan Review Notes For Permit 03040755 |
Permit Number |
03040755 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-24 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) FROM PREVIOUS REVIEW. CLEANOUTS RE- | | QUIRED IN BOTH BREEZWAYS, (STAIRWAYS), | | SHTS P14.01 & P14.03. CLEANOUTS SHALL BE | | FLOOR CLEANOUTS AS THEY ARE REQUIRED TO | | BE TWO WAY CLEANOUTS, OR MORE CLEANOUTS | | WILL BE REQUIRED AT THE UPSTREAM END OF | | THE BLDG DRAIN. 708.5. CLEANOUTS ARE | | REQUIRED TO BE ACCESSIBLE SO THEY SHALL | | BE LOCATED OUTSIDE OF THE UNITS. 708.10 | | 2) SHT P14.07 WATER RISER DIAGRAMS. IF | | WATER HAMMER ARRESTORS ARE INSTALLED AT | | THE WATER HEATERS THEY SHALL BE LOCATED | | AS REQUIRED FOR ALL OTHER WATER HAMMER | | ARRESTORS. PDI-WH 201 & MANUF. INSTALL. | | INSTRUCTIONS. | | 3) SUBMIT A HORIZONTAL SANITARY RISER | | DIAGRAM. SHOW ALL RISER TIE-INS AND | | SHOW DRAINAGE FIXTURE UNITS AS THEY | | ACCUMULATE IN THE SYSTEM. 104.2.1 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|