Plan Review Notes For Permit 03040755 |
Permit Number |
03040755 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-24 00:00:00 | DENIED:BUILDING TYPE I | | | | PLAN SHEET M15.01, INDICATES EXHAUST | | FROM ELEC METER RM HAS A FIRE DAMPER AT | | THE OUTSIDE WALL.THE WALL SEPARATING | | THE ELEC METER RM AND UNIT B2 HAS A FIRE | | RESISTANCE RATING OF 1 HR.A FIRE | | DAMPER IS REQUIRED AT THE PENETRATION | | BETWEEN THE ELEC METER RM & UNIT B2. | | | | PLEASE CLARIFY VENTILATION REQUIREMENTS | | FOR THE CORRIDORS AS PER 2001 FBC(M) | | TABLE 403.3, PUBLIC SPACES - CORRIDORS | | .05 CFM PER SQ FT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|