2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34"
 MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE
 DETAIL PAGE 7.52 DESIGN MANUAL.
 2) ALL UNITS - PLEASE SPECIFY EITHER
 SPECIFICATION "A" OR "B" BATHROOMS AS
 REQUIRED BY DESIGN MANUAL REQUIREMENT
 7B PAGE 7.35
 3) SEPARATE PERMIT REQUIRED FOR IRRIGA-
 TION.
 4) SHT P14.01 CLEANOUTS REQUIRED IN BOTH
 BREEZEWAYS. SECTION 708.3.1 (MAX. 100')
 5) SHT P14.06 RISERS S4 & S5, THE WASTE
 STACH SHALL BE THE SAME SIZE THROUTHOUT
 THE LENGTH OF THE WASTE STACK. SECTION
 910.4.
 6) SHT P14.07 WATER RISER DIAGRAMS, THE
 WATER HAMMER ARRESTORS REQUIRED IN SECT.
 604.9, (ICE MAKER, DISHWASHER. WASH
 MACHINE), SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 7) RPZ BACKFLOW REQUIRED FOR WATER
 SERVICE AT EACH BLDG.
  