2003-05-05 00:00:00 | DENIED: |
| APPARTMENTS |
| |
| 1.PLANS SHEET A15.01 ELEC METER RM, |
| AS PER 2001 FBC(M) 401.5.2, EXHAUST |
| OPENINGS SHALL BE LOCATED AS NOT TO |
| CREATE A NUISANCE.EXHAUST AIR SHALL |
| NOT BE DIRECTED ONTO WALKWAYS. |
| |
| 2.PLEASE INDICATE THE USE OF THE ROOMS |
| WHERE AHU-EL IS LOCATED. |
| |
| 3.CLARIFY EXTERIOR WALL - PLAN SHEET |
| M15.03, INDICATES AN EXHAUST TERMINATION |
| WITH A FIRE DAMPER.PLAN SHEET A1.04 |
| EXTERIOR WALL W1 INDICATES 1 HR, NO FIRE |
| DAMPERS INDICATED ON O.A. INTAKES. |
| |
| 4.PLAN SHEET M15.06 DETAIL OF THE |
| CONDENSATE TRAP CLARIFY VENT CAP IN OPEN |
| PLENUM. |
| |
| 5.PROVIDE OUTSIDE AIR CALCS AS PER |
| 2001 FBC(M) TABLE 403.3 |
| |
| CLUBHOUSE: |
| 1.PLAN SHEET CH M15.01 DRYER EXHAUST |
| PENETRATING RATED WALL AT FIRE PUMP RM, |
| THE IS NOT ACCEPTABLE.FIRE DAMPERS |
| CANNOT BE INSTALLED IN DRYER DUCT DUE |
| TO LINT BUILD-UP. |
| |
| 2.INDICATE WHAT TYPE OF DRYERS ARE TO |
| BE INSTALLED IN THE PUBLIC LAUNDRY ROOM. |
| (COMMERCIAL?) |
| |
| 3.PLEASE NOTE, SHOULD DRYERS IN THE |
| LAUNDRY ROOM EXHAUST GREATER THAN |
| 2,000 CFM, AIR MAKE UP IS REQUIRED. |
| |
| 4.PROVIDE OUTSIDE AIR CALCS AS PER |
| TABLE 403.3. |
| |
| 5.PLEASE CLARIFY THE MOP SINK IN THE |
| AHU CLOSET. |
| |