Plan Review Notes
Plan Review Notes For Permit 03040755
Permit Number 03040755
Review Stop M
Sequence Number 1
Notes
Date Text
2003-05-05 00:00:00DENIED:
 APPARTMENTS
  
 1.PLANS SHEET A15.01 ELEC METER RM,
 AS PER 2001 FBC(M) 401.5.2, EXHAUST
 OPENINGS SHALL BE LOCATED AS NOT TO
 CREATE A NUISANCE.EXHAUST AIR SHALL
 NOT BE DIRECTED ONTO WALKWAYS.
  
 2.PLEASE INDICATE THE USE OF THE ROOMS
 WHERE AHU-EL IS LOCATED.
  
 3.CLARIFY EXTERIOR WALL - PLAN SHEET
 M15.03, INDICATES AN EXHAUST TERMINATION
 WITH A FIRE DAMPER.PLAN SHEET A1.04
 EXTERIOR WALL W1 INDICATES 1 HR, NO FIRE
 DAMPERS INDICATED ON O.A. INTAKES.
  
 4.PLAN SHEET M15.06 DETAIL OF THE
 CONDENSATE TRAP CLARIFY VENT CAP IN OPEN
 PLENUM.
  
 5.PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3
  
 CLUBHOUSE:
 1.PLAN SHEET CH M15.01 DRYER EXHAUST
 PENETRATING RATED WALL AT FIRE PUMP RM,
 THE IS NOT ACCEPTABLE.FIRE DAMPERS
 CANNOT BE INSTALLED IN DRYER DUCT DUE
 TO LINT BUILD-UP.
  
 2.INDICATE WHAT TYPE OF DRYERS ARE TO
 BE INSTALLED IN THE PUBLIC LAUNDRY ROOM.
 (COMMERCIAL?)
  
 3.PLEASE NOTE, SHOULD DRYERS IN THE
 LAUNDRY ROOM EXHAUST GREATER THAN
 2,000 CFM, AIR MAKE UP IS REQUIRED.
  
 4.PROVIDE OUTSIDE AIR CALCS AS PER
 TABLE 403.3.
  
 5.PLEASE CLARIFY THE MOP SINK IN THE
 AHU CLOSET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.