Plan Review Notes For Permit 03040755 |
Permit Number |
03040755 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-09 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO,DURING,AND AFTER CONSTRUCTION. | | | | 2) PLEASE PROVIDE AN OVERALL SITE PLAN | | DISPLAYING ALL EXISTING BUILDINGS AND | | CONDITIONS. | | | | 3) TAMPER SWITCHES,CHAINS AND LOCKS | | ARE REQUIRED ON BACKFLOW DEVICE. | | | | 4) ALL GATE ENTRY SYSTEMS ARE TO BE | | PROPERLY PERMITTED. | | | | 5) KNOX-BOX RAPID ENTRY SYSTEM ARE | | REQUIRED FOR THE BUILDINGS. | | | | 6) BUILDING ADDRESSES REQUIRED. | | | | 7) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR | | WALLS AND CEILINGS OF CLUBHOUSE. | | | | 8) NFPA 13R NOTE DOES NOT APPLY. | | | | 9) THE STANDPIPE SYSTEM SHALL BE | | EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS. | | | | 10) TACTILE SIGNAGE REQUIRED AT | | STAIRWAYS. | | | | 11) ALL SHAFTS THAT ARE LARGE ENOUGH | | FOR PERSONS TO FALL INTO SHALL BE | | MARKED SHAFTWAY. | | | | 12) PLEASE PROVIDE WRITTEN DOCUMENTATION | | THAT EITHER BUILDING WILL NOT BE SOLD | | INDEPENDENTLY FROM THE OTHER ONE SINCE | | ONLY ONE FIRE PUMP IS SHOWN. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|