2003-05-09 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING,AND AFTER CONSTRUCTION.
  
 2) PLEASE PROVIDE AN OVERALL SITE PLAN
 DISPLAYING ALL EXISTING BUILDINGS AND
 CONDITIONS.
  
 3) TAMPER SWITCHES,CHAINS AND LOCKS
 ARE REQUIRED ON BACKFLOW DEVICE.
  
 4) ALL GATE ENTRY SYSTEMS ARE TO BE
 PROPERLY PERMITTED.
  
 5) KNOX-BOX RAPID ENTRY SYSTEM ARE
 REQUIRED FOR THE BUILDINGS.
  
 6) BUILDING ADDRESSES REQUIRED.
  
 7) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR
 WALLS AND CEILINGS OF CLUBHOUSE.
  
 8) NFPA 13R NOTE DOES NOT APPLY.
  
 9) THE STANDPIPE SYSTEM SHALL BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 10) TACTILE SIGNAGE REQUIRED AT
 STAIRWAYS.
  
 11) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO SHALL BE
 MARKED SHAFTWAY.
  
 12) PLEASE PROVIDE WRITTEN DOCUMENTATION
 THAT EITHER BUILDING WILL NOT BE SOLD
 INDEPENDENTLY FROM THE OTHER ONE SINCE
 ONLY ONE FIRE PUMP IS SHOWN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910