Plan Review Notes
Plan Review Notes For Permit 03040657
Permit Number 03040657
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLAN FOR CODE COMPLIANCE.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR FOR
 A 400 AMP SERVICE MUST COMPLY WITH
 250-66.(1/0).
  
 2} THE FEEDERS FOR PANEL "B" MUST
 CONTAIN AN EQUIPMENT GROUND.
  
 3} THE LAUNDRY CIRCUIT ON THE PANEL
 SCHEDULE MUST COMPLY WITH
 220-16(B).1.5KW.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} SMOKE DETECTOR IN THE KITCHEN IS IN
 VIOLATION OF 8-4.1.2 NFPA-72,CHANGE TO A
 LISTED HEAT DETECTOR,OR REMOVE.
  
 6} THE SMOKE DETECTOR IN THE ENTRY TO
 THE MASTER SUITE SHOULD BE LOCATED IN
 THE VESTIBULE TO MEET THE INTENT OF
 ARTICLE 8-1.4.1.6.2(2) AS "OUTSIDE" THE
 SLEEPING AREA.
  
 7} BEDROOM #4 NEEDS A RECEPTACLE TO
 COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718