2003-05-12 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT THE RECEIPT FOR THE COUNTY |
| IMPACT FEES. |
| |
| 3) THE ROOF SHEATHING NAIL SPACING GIVEN |
| ON SHEET GN1 IS INCORRECT. SEE CITY |
| AMENDMENTS TO FBC TABLE 2306.1. |
| |
| 4) REVISE ITEM #7 UNDER STUCCO SPECS. ON |
| A5 TO INDICATE THAT 3/8" HIGH RIB METAL |
| LATH IS REQUIRED TO BE ATTACHED AT EVERY |
| RIB (4"O.C.). SEE ASTM C 1063. |
| ITEMS #4 AND #5 ARE THE SAME NOTE. |
| |
| 5) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF |
| THE 1/2" DIA. EXPANSION ANCHORS AT THE |
| WOOD FRAME TO CONCRETE DETAIL ON A6. THE |
| "USP" TP6X AND TP8X THAT ARE SPECIFIED |
| AT EACH END OF THE STUDS DO NOT APPEAR |
| IN THE 2003 USP CATALOG. SHOULD THESE BE |
| "USP" SPT6 OR SPT8 ? |
| |
| 6) THE GIRDER TRUSS AT THE SECOND FLOOR |
| ABOVE BEDROOM #2 WITH AN UPLIFT OF 5455# |
| AND BEARING ON THE (3) 2X6S HAS THE |
| WRONG CONNECTOR SPECIFIED. THE DETAIL |
| SPECIFIED IS F ON S3. THIS DETAIL IS OF |
| A "USP" USC 53 ATTACHED TO A MASONRY |
| WALL. PLEASE CORRECT. |
| |
| 7) PROVIDE A DIAGRAM INDICATING THE ROOF |
| SHEATHING NAILING ZONES. SEE CITY AMEND. |
| TO FBC TABLE 2306.1. |
| |
| 8) PROVIDE A SOIL BEARING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| |
| 9) THE ENERGY CALCULATION FORM CONTAINS |
| ERRORS. THE ADJACENT WALLS ON THE PLANS |
| ARE CONCRETE BLOCK NOT WOOD FRAME. THE |
| SQUARE FOOTAGE LISTED FOR THE EXTERIOR |
| WOOD FRAME WALLS IS TOO MUCH. THE OWNER |
| AND BUILDER INFORMATION LISTED IS |
| INCORRECT. PLEASE CORRECT. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |