Plan Review Notes
Plan Review Notes For Permit 03040609
Permit Number 03040609
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-06 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 3) THE COVERED PATIO SHOWN ON THE SURVEY
 DOES NOT MATCH THE ONE THAT IS SHOWN ON
 THE PLANS.
  
 4) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF
 THE 1/2" DIAMETER EXPANSION ANCHORS
 USED AT THE WOOD FRAME TO CONCRETE WALL
 CONNECTION ON SHEET A6.
  
 5) THE COLUMN SCHEDULE ON S1 SPECIFIES
 A C2 COLUMN OF TWO 2X4 WOOD POST AND THE
 NOTE ON THE FOUNDATION PLAN ON S1 AT THE
 C2 LOCATION CALLS FOR THREE 2X4 WOOD
 POST. PLEASE CORRECT.
  
 6) STRESS INCREASES FOR SHORT TERM
 LOADING OF STEEL IS NO LONGER ALLOWED TO
 BE TAKEN BY FBC 1609.4.3. SEE THE 2003
 USP CATALOG FOR LOAD VALUES THAT DO NOT
 INCLUDE A STRESS INCREASE ON THE STEEL
 CALCULATIONS. PLEASE REVISE THE
 CONNECTOR UPLIFT VALUES ACCORDINGLY.
  
 7) REVISE NOTE 7 UNDER EXTERIOR SOFFIT
 SPECS. ON A5 TO INDICATE THAT 3/8" HIGH
 RIB METAL LATH IS REQUIRED TO BE
 FASTENED AT EACH RIB (4"O.C.) AS
 REQUIRED BY ASTM C 1063.
  
 8) PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS.
  
 9) ONE OF THE ENGINEERED PRODUCT
 APPROVALS FOR THE DESIGNER SHAPED FIXED
 GLASS WINDOWS IS MISSING FROM THE
 SUBMITTALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202