2003-05-06 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE A SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| |
| 3) THE COVERED PATIO SHOWN ON THE SURVEY |
| DOES NOT MATCH THE ONE THAT IS SHOWN ON |
| THE PLANS. |
| |
| 4) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF |
| THE 1/2" DIAMETER EXPANSION ANCHORS |
| USED AT THE WOOD FRAME TO CONCRETE WALL |
| CONNECTION ON SHEET A6. |
| |
| 5) THE COLUMN SCHEDULE ON S1 SPECIFIES |
| A C2 COLUMN OF TWO 2X4 WOOD POST AND THE |
| NOTE ON THE FOUNDATION PLAN ON S1 AT THE |
| C2 LOCATION CALLS FOR THREE 2X4 WOOD |
| POST. PLEASE CORRECT. |
| |
| 6) STRESS INCREASES FOR SHORT TERM |
| LOADING OF STEEL IS NO LONGER ALLOWED TO |
| BE TAKEN BY FBC 1609.4.3. SEE THE 2003 |
| USP CATALOG FOR LOAD VALUES THAT DO NOT |
| INCLUDE A STRESS INCREASE ON THE STEEL |
| CALCULATIONS. PLEASE REVISE THE |
| CONNECTOR UPLIFT VALUES ACCORDINGLY. |
| |
| 7) REVISE NOTE 7 UNDER EXTERIOR SOFFIT |
| SPECS. ON A5 TO INDICATE THAT 3/8" HIGH |
| RIB METAL LATH IS REQUIRED TO BE |
| FASTENED AT EACH RIB (4"O.C.) AS |
| REQUIRED BY ASTM C 1063. |
| |
| 8) PROVIDE PRODUCT APPROVAL FOR SLIDING |
| GLASS DOORS. |
| |
| 9) ONE OF THE ENGINEERED PRODUCT |
| APPROVALS FOR THE DESIGNER SHAPED FIXED |
| GLASS WINDOWS IS MISSING FROM THE |
| SUBMITTALS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |