2003-05-06 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 3) THE COVERED PATIO SHOWN ON THE SURVEY
 DOES NOT MATCH THE ONE ON THE PLANS.
  
 4) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF
 THE 1/2" DIAMETER EXPANSION ANCHORS USED
 AT THE WOOD FRAME TO CONCRETE WALL
 CONNECTION ON SHEET A6.
  
 5) THE COLUMN SCHEDULE ON S1 SPECIFIES
 A C2 COLUMN AS A TWO 2X4 WOOD POST. THE
 NOTE ON THE FOUNDATION PLAN ON S2,
 SPECIFIES A THREE 2X4 WOOD POST. PLEASE
 CORRECT.
  
 6) STRESS INCREASES FOR SHORT TERM
 LOADING OF STEEL ARE NO LONGER ALLOWED
 TO BE TAKEN BY FBC 1609.4.3. SEE THE
 2003 FBC CATALOG FOR LOAD VALUES THAT DO
 NOT INCLUDE A STRESS INCREASE ON THE
 STEEL CALCULATIONS. PLEASE REVISE THE
 CONNECTOR UPLIFT VALUES ACCORDINGLY.
  
 7) REVISE NOTE 7 UNDER EXTERIOR SOFFIT
 SPECS. TO INDICATE THAT 3/8" HIGH RIB
 METAL LATH IS REQUIRED TO BE FASTENED
 AT EVERY RIB (4"O.C.) PER ASTM C 1063.
 NOTES 4 AND 5 ARE THE SAME.
  