2003-05-06 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE A SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| |
| 3) THE COVERED PATIO SHOWN ON THE SURVEY |
| DOES NOT MATCH THE ONE ON THE PLANS. |
| |
| 4) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF |
| THE 1/2" DIAMETER EXPANSION ANCHORS USED |
| AT THE WOOD FRAME TO CONCRETE WALL |
| CONNECTION ON SHEET A6. |
| |
| 5) THE COLUMN SCHEDULE ON S1 SPECIFIES |
| A C2 COLUMN AS A TWO 2X4 WOOD POST. THE |
| NOTE ON THE FOUNDATION PLAN ON S2, |
| SPECIFIES A THREE 2X4 WOOD POST. PLEASE |
| CORRECT. |
| |
| 6) STRESS INCREASES FOR SHORT TERM |
| LOADING OF STEEL ARE NO LONGER ALLOWED |
| TO BE TAKEN BY FBC 1609.4.3. SEE THE |
| 2003 FBC CATALOG FOR LOAD VALUES THAT DO |
| NOT INCLUDE A STRESS INCREASE ON THE |
| STEEL CALCULATIONS. PLEASE REVISE THE |
| CONNECTOR UPLIFT VALUES ACCORDINGLY. |
| |
| 7) REVISE NOTE 7 UNDER EXTERIOR SOFFIT |
| SPECS. TO INDICATE THAT 3/8" HIGH RIB |
| METAL LATH IS REQUIRED TO BE FASTENED |
| AT EVERY RIB (4"O.C.) PER ASTM C 1063. |
| NOTES 4 AND 5 ARE THE SAME. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |