2003-05-02 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) PROVIDE A SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND.TO FBC 1804.2.2. |
| |
| 4) THE COVERED PATIO SHOWN ON THE |
| SURVEY DOES NOT MATCH THE PLANS. |
| |
| 5) SPECIFY THE LENGTH/EMBEDMENT DEPTH |
| OF THE 1/2" DIAMETER EXPANSION ANCHORS |
| USED AT THE WOOD FRAME TO CONCRETE WALL |
| CONNECTION ON SHEET A6. |
| |
| 6) THE COLUMN SCHEDULE ON S1 SPECIFIES A |
| TWO (2) 2X4 POST FOR C2. THE NOTE ON THE |
| FOUNDATION PLAN AT THE C2 LOCATION CALLS |
| FOR A THREE (3) 2X4 POST. |
| PLEASE CORRECT. |
| |
| 7) STRESS INCREASES FOR SHORT TERM |
| LOADING ON STEEL ARE NO LONGER ALLOWED |
| TO BE TAKEN BY FBC 1609.4.3. SEE THE |
| 2003 USP CATALOG FOR LOAD VALUES THAT DO |
| NOT INCLUDE A STRESS INCREASE ON THE |
| STEEL CALCULATIONS. PLEASE REVISE THE |
| CONNECTOR UPLIFT VALUES ACCORDINGLY. |
| |
| 8) NOTE 7 UNDER EXTERIOR SOFFIT SPECS. |
| ON A5 DOES NOT INDICATE THAT 3/8" HIGH |
| RIB METAL LATH IS REQUIRED TO BE |
| FASTENED AT EACH RIB (4"O.C.) PER |
| ASTM C 1063. PLEASE CORRECT. |
| NOTES 4 AND 5 ARE THE SAME. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |