Plan Review Notes
Plan Review Notes For Permit 03040604
Permit Number 03040604
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-02 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND.TO FBC 1804.2.2.
  
 4) THE COVERED PATIO SHOWN ON THE
 SURVEY DOES NOT MATCH THE PLANS.
  
 5) SPECIFY THE LENGTH/EMBEDMENT DEPTH
 OF THE 1/2" DIAMETER EXPANSION ANCHORS
 USED AT THE WOOD FRAME TO CONCRETE WALL
 CONNECTION ON SHEET A6.
  
 6) THE COLUMN SCHEDULE ON S1 SPECIFIES A
 TWO (2) 2X4 POST FOR C2. THE NOTE ON THE
 FOUNDATION PLAN AT THE C2 LOCATION CALLS
 FOR A THREE (3) 2X4 POST.
 PLEASE CORRECT.
  
 7) STRESS INCREASES FOR SHORT TERM
 LOADING ON STEEL ARE NO LONGER ALLOWED
 TO BE TAKEN BY FBC 1609.4.3. SEE THE
 2003 USP CATALOG FOR LOAD VALUES THAT DO
 NOT INCLUDE A STRESS INCREASE ON THE
 STEEL CALCULATIONS. PLEASE REVISE THE
 CONNECTOR UPLIFT VALUES ACCORDINGLY.
  
 8) NOTE 7 UNDER EXTERIOR SOFFIT SPECS.
 ON A5 DOES NOT INDICATE THAT 3/8" HIGH
 RIB METAL LATH IS REQUIRED TO BE
 FASTENED AT EACH RIB (4"O.C.) PER
 ASTM C 1063. PLEASE CORRECT.
 NOTES 4 AND 5 ARE THE SAME.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202