2003-05-20 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT THE PAID RECEIPT FOR THE |
| IMPACT FEES. |
| |
| 3) SUBMIT A SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| |
| 4) THE OWNER INFORMATION LISTED ON THE |
| APPLICATION DOES NOT MATCH THE OWNER OF |
| RECORD WITH THE CITY OR COUNTY. |
| |
| 5) THE OWNER AND CONTRACTOR INFORMATION |
| ON THE ENERGY CALCULATIONS DOES NOT |
| MATCH THE APPLICATION OR CITY RECORDS. |
| |
| 6) REVISE STUCCO NOTES ON A5. SPECIFY |
| THE FASTENER SIZE IN NOTE 3. INDICATE IN |
| NOTE 7 THAT 3/8" HIGH RIB METAL LATH IS |
| REQUIRED TO BE FASTENED AT EVERY RIB |
| (4"O.C.). NOTES 4 AND 5 ARE EXACTLY THE |
| SAME. |
| |
| 7) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF |
| THE 1/2" DIAMETER EXP. ANCHORS AT THE |
| WOOD FRAME TO CONCRETE WALL DETAIL ON A6 |
| UPDATE THE SEMCO TPP4 OR TPP6 CONNECTORS |
| SEMCO WAS PURCHASED BY USP. |
| |
| 8) THE COLUMN SCHEDULE ON S-1 LISTS C2 |
| AS (2) 2X4 POSTS AND THE NOTE ON THE |
| FOUNDATION PLAN SPECIFIES (3) 2X4 WOOD |
| POSTS AT C2. PLEASE CLARIFY. |
| |
| 9) THE SURVEYS SUMITTED DO NOT MATCH THE |
| PLANS AT THE COVERED PATIO. |
| |
| 10) REVISE THE UPLIFT VALUES FOR THE |
| TRUSS CONNECTORS TO REFLECT THE VALUES |
| THAT DO NOT HAVE STRESS INCREASES FOR |
| THE STEAL CALCULATIONS. SEE 2003 USP |
| CATALOG AND FBC 1609.4.3. |
| |
| 11) ONE OF THE LOCATIONS WHERE THE STEEL |
| COLUMN CAP DETAIL 4 ON S2 IS SPECIFIED |
| IS SHOWN ON THE FLOOR PLAN CARRYING TWO |
| GIRDERS AT 90 DEGREE ANGLES. THIS IS NOT |
| INDICATED BY THE DETAIL. |
| |
| 12) DETAIL 1 ON S2 DOES NOT INDICATE HOW |
| THE FLOOR TRUSS IS ATTACHED TO THE BLOCK |
| WALL. |
| |
| 13) THE "USP" RT20T CONNECTOR IN DETAIL |
| 3 ON S2 REQUIRES (14) NAILS EQUALLY |
| DISTRIBUTED ON EACH SIDE OF THE |
| CONNECTION PER USP CATALOG. |
| |
| 14) THE ROOF SHEATHING NAILING ZONE |
| DIAGRAM DOES NOT INDICATE THAT THE |
| GABLE ENDS AT THE GARAGE AND SECOND |
| FLOOR BATHROOM ARE ZONE 3. |
| |
| 15) SUBMIT PRODUCT APPROVALS FOR THE |
| SLIDING GLASS DOORS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |