2003-04-25 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RESUBMIT ENERGY CALCULATIONS WITH
 ENGINEER'S ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.
 2-RESUBMIT STORM PANELS INFORMATION WITH
 UPDATED SBCCI REPORT THAT MATCHES
 ENGINEERED DRAWINGS. CHECK THE DESIGN
 PRESSURES AND THE MAX/MIN PANEL SPAN
 SHOWN ON THE INSTALLATION SCHEDULE AND
 THOSE SHOWN ON THE ENGINEERED DWGS AND
 REVISE AS REQUIRED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 3-REVISE/CLARIFY DETAIL S26 TO MATCH
 THOSE CONDITIONS AS SHOWN ON SECOND
 FLOOR FRAMING PLAN. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.