2003-04-25 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RESUBMIT ENERGY CALCULATIONS WITH THE
 ENGINEER'S ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.
 2-RESUBMIT STORM PANELS INFORMATION WITH
 UPDATED SBCCI REPORT THAT MATCHES THE
 ENGINEERED DRAWINGS. CHECK AND REVISE
 THE DESIGN PRESSURES AND PANEL SPAN ON
 THE INSTALLATION SCHEDULE TO MATCH
 CONDITIONS SHOWN ON THE ENGINEERED
 DRAWINGS. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 3-REVISE/CLARIFY DETAIL S26 TO MATCH
 CONDITIONS SHOWN ON SECOND FLOOR
 FRAMING PLAN. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.