Plan Review Notes For Permit 03040396 |
Permit Number |
03040396 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-03 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE PRODUCT APPROVAL FOR SINGLE | | HUNG WINDOWS WHERE DRAWINGS MATCH THE | | REPORT. (2 COPIES) | | 2-PROVIDE PRODUCT APPROVAL FOR STORM | | SHUTTERS WITH LEGIBLE DRAWINGS. | | (2 COPIES). | | 3-MAKE SURE BEDROOM EGRESS WINDOWS HAVE | | 20" MIN. CLEAR WIDTH, 24"MIN. CLEAR | | HEIGHT AND 5S.F. MIN. CLEAR OPENING AS | | REQUIRED BY SEC. 1005.4.4 FBC 2001. |
|