Plan Review Notes
Plan Review Notes For Permit 03040131
Permit Number 03040131
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-10 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/
 PANEL AND NOTES.
 RISER NOTES MENTIONS, MAIN TO BE 225A,
 RISER AND PANEL SHOWS 200A?
 PLEASE ALSO SEE SUB PANEL, SHOWS 65A MLO
 AND MAIN PANEL SHOWS AS 60A?
 PLEASE CORRELATE
  
 2)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPT. 210-52C-1
  
 3)NOTE: PLEASE SEE MISSING HALLWAY
 RECEPT. IN MASTER BEDROOM? 210-52H
  
 4)NOTE: PLEASE SHOW ROOM DESIGNATIONS,
 ON PLANS.
  
 5)NOTE: PLEASE SEE SUB PANEL, SHOWS
 SM APPL CIRCUITS AS 2 CIRCUITS W/ LOAD
 SHOWN FOR THREE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]