Plan Review Notes For Permit 03040131 |
Permit Number |
03040131 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-10 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/ | | PANEL AND NOTES. | | RISER NOTES MENTIONS, MAIN TO BE 225A, | | RISER AND PANEL SHOWS 200A? | | PLEASE ALSO SEE SUB PANEL, SHOWS 65A MLO | | AND MAIN PANEL SHOWS AS 60A? | | PLEASE CORRELATE | | | | 2)NOTE: PLEASE SEE MISSING KITCHEN | | COUNTERSPACE RECEPT. 210-52C-1 | | | | 3)NOTE: PLEASE SEE MISSING HALLWAY | | RECEPT. IN MASTER BEDROOM? 210-52H | | | | 4)NOTE: PLEASE SHOW ROOM DESIGNATIONS, | | ON PLANS. | | | | 5)NOTE: PLEASE SEE SUB PANEL, SHOWS | | SM APPL CIRCUITS AS 2 CIRCUITS W/ LOAD | | SHOWN FOR THREE? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | [email protected] |
|