Plan Review Notes For Permit 03040127 |
Permit Number |
03040127 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-10 00:00:00 | ************* UNSAT ****************** | | | | 1)NOTE: PLEASE SIZE FEEDER FROM MAIN | | TO PANEL PER 310-15/310-16. SHOWN AS#2? | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTED CIRCUITS ON PANEL SCHEDULE. | | PER 210-12 | | | | 3)NOTE: PLEASE SEE MISSING RECEPT ON | | KITCHEN COUNTERSPACE. PER 210-52C-1 | | | | 4)NOTE: PLEASE ALSO SEE MISSING RECEPT | | FOR KITCHEN ISLAND. 210-52C-2 | | | | 5)NOTE: PLEASE MOVE SD INTO MASTER | | BEDROOM AREA.SD NOT TO BE IN BATHS/ | | AREAS NFPA-72 8-1.4.2 | | | | 6)NOTE: PLEASE PROVIDE ROOM DESIGNATION | | ON PLAN. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | EELCTRICAL PLAN REVIEW | | 561-659-8096 EXT8372 | | [email protected] |
|