Notes
Date Text
2003-04-10 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SIZE FEEDER FROM MAIN
 TO PANEL PER 310-15/310-16. SHOWN AS#2?
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE.
 PER 210-12
  
 3)NOTE: PLEASE SEE MISSING RECEPT ON
 KITCHEN COUNTERSPACE. PER 210-52C-1
  
 4)NOTE: PLEASE ALSO SEE MISSING RECEPT
 FOR KITCHEN ISLAND. 210-52C-2
  
 5)NOTE: PLEASE MOVE SD INTO MASTER
 BEDROOM AREA.SD NOT TO BE IN BATHS/
 AREAS NFPA-72 8-1.4.2
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON PLAN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW
 561-659-8096 EXT8372
 [email protected]