Plan Review Notes
Plan Review Notes For Permit 03040117
Permit Number 03040117
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-24 00:00:00BUILDING REVIEW APPORVED WITH PROVISO:
 1-RESUBMIT ENERGY CALCULATIONS WITH THE
 ENGINEER ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.
 2-RESUBMIT STORM PANELS INFORMATION WITH
 UPDATED SBCCI PRODUCT APPROVAL REPORT
 THAT MATCHES ENGINEERED DRAWINGS.
 CHECK DESIGN PRESSURES AND
 MAX/MIN PANEL SPAN SHOWN ON DRAWINGS
 AND THE ONES IN THE INSTALLATION
 SCHEDULE. REVISE AS REQUIRED.
 3-REVISE/CLARIFY DETAIL S-26 TO MATCH
 CONDITIONS SHOWN ON 2ND FLOOR FRAMING
 PLAN. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.